Replacement sensor pack' module for first alert carbon monoxide alarms model fcd1, fcd1ac, nico, nicoac, faco, facoac and brk electronics’ models brkdco, brkco, c01000b. co1120b and family gartf (2 pages)
Page 1
Control / Communicator ARMED READY BS/ESC ARMED READY SHIFT SPAC NT R FA 5 6 0 AWAY STAY BYPASS T ST INSTANT CHIM R ADY FA260 N8026-1V2 3/10 Rev A...
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • General Information The FA2000C provides features that allow the system to comply with UL864 installation requirements. The following features must be set accordingly in order for the system to comply with...
About the FA2000C The First Alert FA2000C is a fire alarm control/communicator that supports 5 style B (for further explanation of style B, refer to NFPA 72 National Fire Alarm Code Chapter 3: Protected Premises Fire Alarm Systems) hardwired zones. It may be used as a slave Digital Alarm Communicator Transmitter (DACT) providing central station or remote station service for a listed Fire Alarm Control Panel (FACP).
Page 8
FA2000C Installation and Setup Guide Built-in Indicators and Switches • A built-in warning buzzer that provides alarm, supervisory, and trouble sounds • 10 LED indicators provide visual status of (1) AC Power, (2) Battery Trouble, (3) Communication Failure, (4) Telco...
S E C T I O N Installing the Control • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • This section describes the procedures for mounting and wiring the control panel and all the peripheral devices.
FA2000C Installation and Setup Guide Slip the bottom part of the circuit board onto the 3 lower Standoffs ensuring it is under the lock washers. Then snap the top part of the circuit board onto the 2 upper Standoffs. Tighten the 3 screws securing the circuit board to the 3 lower Standoffs.
Section 2 – Installing the Control Back Cabinet Standoff Standoff Plate Door LED Indicator Board Standoffs Facility Ground Wires must be run in Conduit Battery Battery Wired to Transformer Figure 2-3: Circuit Board Installation Commercial Fire Installation Guidelines • Dress field wiring away from the microprocessor (center) section of the PC board. Dress wiring to the left and right sides of the cabinet and secure using tie wraps.
Fixed-Word Display: FA260KP, and/or Alpha Display: FA570KP • Independent of the restrictions on keypads for stand-alone control usage, the FA2000C supports up to 4 keypads • provided that the 350mA current rating is not exceeded for aux. power and for the system as a whole. Fixed word and alpha keypads may be used in the same installation.
• The bell output must be used for fire alarm annunciation when the FA2000C is used as a stand alone local control. Unless otherwise specified by the local AHJ, use of the bell output is not required for all other DACT and stand alone control installations.
Page 14
FA2000C Installation and Setup Guide SOUNDER TYPE MANUFACTURER MODEL # SOUNDER TYPE MANUFACTURER MODEL # 2-Wire Wall Mount SYSTEM SENSOR P2RK Ceiling Mount Strobe, 12/24V, High SYSTEM SENSOR SCRH Horn/Strobe, 12/24V, Candela, Red Standard Candela, Red, Outdoor 2-Wire Wall Mount...
Auxiliary Relay Connections provides on auxiliary relay output which may be configured as one of the following: FA2000C • Wet 12VDC form C relay output Dry, unsupervised form C relay with contacts rated at 30VAC/VDC, 2A max. resistive loads •...
Telephone Line Connections The FA2000C provides two supervised dialer outputs: the main dialer and the back-up dialer. In fire installations, both outputs must be connected to separate telephone lines providing loop start service. Connect the main dialer and back-up dialer (if used) outputs to telephone company lines using the RJ31X cables...
Dialer Operation When only the main dialer is enabled (1, 0 in field 79), the FA2000C will attempt to route all calls over the main output. When both main and back-up dialers are enabled (1,1 in field 79), the FA2000C will attempt to route all calls over the main output unless a fault is detected, at which time it will attempt to use the back-up output.
Page 18
FA2000C Installation and Setup Guide Connect closed circuit devices in series in the high (+) side the loop. The 2,000 ohm EOL resistor must be connected • in series with the devices, following the last device. See the Summary of Connections diagram.
Page 19
This model may not be used on zones designated as Zone Type 16: Fire with Verification. • These smoke detectors are UL Listed for use with the FA2000C, and are the only 2-wire smoke detectors that may be used. •...
Silence/Reset key or enter the User's Code + [OFF] again. Determining the Control’s Power Supply Load In the event of an AC power loss the FA2000C must be supported by a backup, rechargeable 12VDC 7AH min./14AH max. battery. The battery's capacity must be sized to provide 24 hours (UL Central Station Fire) or 60 hours (UL Remote Station Fire) of standby time followed by 6 minutes of alarm time.
Total Current Standby Alarm Auxiliary Power Subtotal Bell Output Subtotal Auxiliary Relay Output Subtotal FA2000C PCB Current (Includes 2-wire smoke detector and LED indicator PCB 155mA 235mA currents) Total Current Load (350mA max. standby; 1.0A max. alarm) NOTE: Limit the total power supply standby current to 210mA when a 60-hour standby time is desired.
7. Connect the battery, referring to Figure 2-10. The FA2000C runs a brief battery test once a minute to determine if battery leads are connected and runs an extended battery test every 24 hours to determine if battery capacity is low (less than approximately 11.5VDC). If a low battery condition exists the FA2000C's built-in Battery Trouble LED will light and a rapid beeping sound will be heard from its built-in warning buzzer.
S E C T I O N Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Entering and Exiting Programming Mode Enter Programming mode using either method a or b: Exit the Programming mode by either method a or b:...
Exits menu mode, back into field programming mode, when 00+[] entered at the first question for each category. Zone Number Designations The FA2000C supports up to 5 zones. The following table lists the zone numbers, their functions and the Zone Function Default default.
S E C T I O N Data Field Descriptions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Data Field Programming The following pages list this control’s data fields in numerical order.
Page 26
FA2000C Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION If 1 , the system produces a supervisory condition on both an open and a Supervisory on Open/Short short. If 0, the system produces a trouble condition on an open and a 0 = trouble on open/supervisory on short supervisory condition on a short.
Page 27
Section 4 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION Select the type of split/dual reporting for system communication. Split/Dual Reporting 0 = backup reporting only 1 = alarm, alarm restore, reports to primary, all others to secondary 2 = all except test reports to primary, test to secondary 3 = alarm, alarm restore, reports to primary,...
Page 28
FA2000C Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION Enter the report code for a trouble condition. Trouble Report Code Enter the report code when a zone is manually bypassed. Bypass Report Code Enter the report code for an ac loss condition. This report is sent at a random AC Loss Report Code ...
Page 29
Section 4 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION This field has two entries, one for each dialer (main and backup). Enter 1 if Main/Backup Dialer Enable the dialer is being used. 0 = disable 1 = enable See the SECTION 5: Menu Mode Programming for detailed information on Custom Alpha Editing ...
S E C T I O N Menu Mode Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • General Information The Menu Mode Programming is an interactive mode through which much of the system’s zone and alpha programming is done.
Zone Type to re-enable it. Field 82 Zone Programming The alpha keypad used with the FA2000C can have a user-friendly English language description/location of all protection zones and keypad emergency zones programmed into the system. Each description can be composed of a combination of words (up to a maximum of 3) selected from a vocabulary of 249 words stored in memory (listed later in this section).
Page 33
Section 5 – Menu Mode Programming PROMPT EXPLANATION To delete or change the default descriptor for zone 1, press plus the same zone number (01). Flashing Cursor (system is ready for This will clear that descriptor and gain access to the entry mode with flashing cursor, allowing entry of word).
FA2000C Installation and Setup Guide Adding Custom Words You can add up to five installer-defined words to the built-in vocabulary. Each of the five "words" can actually consist of a "word string" of one or more words, but no more than ten characters can be used for each word or word string.
The FA2000C has two dialers – a main and a back-up dialer. Each of these is enabled separately in program field 79 (both are enabled by default). If enabled, the back-up dialer will only become active when a line fault (voltage on the main dialer drops below 2 volts) is sensed.
S E C T I O N Downloading Primer (Remote Downloading is not a UL Listed feature) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • General Information Downloading allows the operator to remotely access, Access Security...
FA2000C Installation and Setup Guide Getting On-Line with a Control Panel NOTES: It is a UL864 requirement that the panel notify The Installer must be on premises during a • the Central Station whenever an attempt to download. enter the program mode is made.
FA2000C Installation and Setup Guide Keypad Functions The keypad, if used, allows the user to silence alarm and trouble sounders and perform other system functions, such as bypassing zones, and display zone descriptors. Zone and system conditions (alarm, trouble, bypass) are displayed in the Display Window.
(Auxiliary relay will also ding if set for alarm function 1 in field 34 and if assigned in field 85 to the fire zone that was faulted.) The keypads will also display the faulted zone for as long as the fault remains. The FA2000C will initiate an automatic smoke detector reset 10 seconds after a smoke detector has been faulted in order to reset that smoke.
FA2000C Installation and Setup Guide "Check" and "Battery" Displays When the problem has been corrected, the display can be cleared by pressing the Silence/Reset key or by entering code plus off a second time. A display of "CHECK" accompanied by a zone number means there is an open circuit condition on a fire zone, or that there is a system trouble.
Page 45
Note the proper model number of this product, and the version level (if known) along with any documentation that • came with the product. Note your First Alert customer number and/or company name. • Having this information handy will make it easier for us to serve you quickly and effectively.
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • The FA2000C may be used as a slave DACT providing central or remote station service for a central or remote station listed local FACP.
Page 48
FA2000C Installation and Setup Guide IN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMS In the event of telephone operational problems, disconnect the control panel by removing the plug from the RJ31X (CA38A in Canada) wall jack. We recommend that you demonstrate disconnecting the phones on installation of the system.
Page 49
CANADIAN EMISSIONS STATEMENTS This Class B digital apparatus complies with Canadian ICES-003 NOTICE AVIS The Industry Canada Label identifies certified L’étiquette d’Industrie Canada identifie equipment. This certification means that the matériel homologué. Cette étiquette certifie que le equipment meets telecommunications network matériel est conforme aux normes de protection, protective, operational and safety requirements as d’exploitation et de sécurité...
12-1/2" W x 14-1/2" H x 3" D (318mm x 368mm x 76mm) Electrical: Voltage Input: From built-in transformer supplying 18VAC at 40VA to FA2000C. Transformer requires nominal 120VAC, 600mA input. Rechargeable Back-Up Battery: 12VDC, 7AH min., 14AH, max. (Gel type).
..............6-1 CHARACTER LIST ............5-4 Hardwire and Optional Expansion Zones.......1-1 Charging Voltage ............B-1 HAYES modem specified by First Alert......1-2 Check 11 ............... 9-2 Check 12 back-up dialer..........9-2 Circuit breaker protection ..........2-8 Comm. Failure (FC)..........6-1, 9-2 Installing the Control's Circuit Board ......2-1...
WARNING! THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced wireless security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a vari- ety of reasons.
Page 64
DOCUMENTATION AND ONLINE SUPPORT For the latest documentation and online support information, please go to: http://www.security.honeywell.com/hsc/resources/MyWebTech/ WARRANTY For the latest warranty information, please go to: http://www.firstalertprofessional.com/drz 2 Corporate Center Drive, Suite 100 P.O. Box 9040, Melville, NY 11747 Copyright 2010 Honeywell International Inc. www.firstalertprofessional.com ÊN8026-1V2vŠ...
Need help?
Do you have a question about the FA2000C and is the answer not in the manual?
Questions and answers