Installing External Sounders - First Alert FA2000C Installation And Setup Manual

Hide thumbs Also See for FA2000C:
Table of Contents

Advertisement

Installing External Sounders

The FA2000C provides one notification appliance circuit output rated 12VDC nominal (10-14VDC), 1A maximum, which
may be connected to 12V alarm indicating devices (horns, bells, sirens, etc.). This output may be configured for Style Y
EOLR supervision or no supervision and is intended for use as a supervised fire alarm indicating circuit.
The bell output must be used for fire alarm annunciation when the FA2000C is used as a stand alone local
control. Unless otherwise specified by the local AHJ, use of the bell output is not required for all other DACT and
stand alone control installations. When used, the bell should be configured for supervision. 24 hour non-fire
alarms (ex. type 07) must be programmed to activate the auxiliary relay output and not the bell output.
The total alarm current that can be drawn from the bell, auxiliary relay, and auxiliary power outputs combined
must not exceed 1A.
Commercial fire alarm systems require Notification Appliance Circuit to be supervised.
U L
This control complies with National Fire Protection Association (NFPA) requirements for temporal pulse
sounding of fire notification appliances.
Notification Appliance Circuit Supervision
When supervision is enabled, the FA2000C monitors the Notification Appliance Circuit wiring for open and short circuit
faults while the output is inactive. The system provides a trouble indication on Zone 6 (Zone 6 must be programmed for
a 24-hour response type) when an open occurs; or when a short occurs between the Bell (+) and Bell (-) terminal wiring,
or between the Bell (+) terminal wiring and earth ground.
Wiring the Alarm Output
The wiring of the Notification Appliance Circuit depends upon whether you are going to supervise the circuit
or not. Use the appropriate procedure below for your application.
U L
Use only UL Listed sounding devices for UL installations.
Compatible Alarm Indicating Devices
SOUNDER TYPE
UL listed Grade A Bell in
Housing
RX7 UL Indoor Sounder, 12V
Chime, 12/24V, Selectable
Tone & Volume, Red
Chime, 12/24V, Selectable
Tone & Volume, White
Chime/Strobe, 12/24V,
Selectable Candela, Tone &
Volume, Red
Chime/Strobe, 12/24V,
Selectable Candela, Tone &
Volume, White
Horn, 12/24V, Red
Horn, 12/24V, White
Horn, 12/24V, Outdoor, Red
2-Wire Wall Mount
Horn/Strobe, 12/24V,
Standard Candela, Red
2-Wire Wall Mount
Horn/Strobe, 12/24V, High
Candela, Red
MANUFACTURER
MODEL #
Honeywell/ ADEMCO
AB12M-ADT
ADT
875936B
SYSTEM SENSOR
CHR
SYSTEM SENSOR
CHW
SYSTEM SENSOR
CHSR
SYSTEM SENSOR
CHSW
SYSTEM SENSOR
HR
SYSTEM SENSOR
HW
SYSTEM SENSOR
HRK
SYSTEM SENSOR
P2R
SYSTEM SENSOR
P2RH
SOUNDER TYPE
4-Wire Ceiling Mount Horn/Strobe,
12/24V, Standard Candela, Red,
Outdoor
4-Wire Ceiling Mount Horn/Strobe,
12/24V, High Candela, Red, Outdoor
4-Wire Ceiling Mount Horn/Strobe,
12/24V, Standard Candela, White
4-Wire Ceiling Mount Horn/Strobe,
12/24V, High Candela, White
2-Wire Wall Mount Strobe, 12/24V,
Standard Candela, Red
2-Wire Wall Mount Strobe, 12/24V,
High Candela, Red
Wall Mount Strobe, 12/24V, Standard
Candela, Red, Outdoor
Wall Mount Strobe, 12/24V, High
Candela, Red, Outdoor
Wall Mount Strobe, 12/24V, Standard
Candela, White
Wall Mount Strobe, 12/24V, High
Candela, White
Ceiling Mount Strobe, 12/24V,
Standard Candela, Red
Section 2 – Installing the Control
MANUFACTURER
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
SYSTEM SENSOR
MODEL #
PC4RK
PC4RHK
PC4W
PC4WH
SR
SRH
SRK
SRHK
SW
SWH
SCR
2-5