Page 9
Refer to the section on System Communications for more information on related programming. An FA550KP must be used to program the FA2000C locally. Refer to the sections on Mechanics of Programming and Data Field Descriptors, as well as the Program Form for details on the various programming options.
Page 10
SLOTS RETAINER CLIP UNLOCKED CABINET DOOR BOTTOM Figure 1. Installing The Cabinet Lock black DETAIL A SIDE VIEW OF BOARD INSERTED INTO SLOTS DETAIL B SIDE VIEW OF SHORT MOUNTING CLIPS Figure 2: Mounting the FA2000C PC Board – 10–...
Page 14
Figure 3: Keypad Connections To The Control Board – 14–...
Page 15
REMOTE PROGRAMMING AND CONTROL (DOWNLOADING) Before programming data fields for the first time, enter *97 to load factory defaults! Then press *96 if downloading is to be performed. – 15–...
Page 18
MUST POWER DETECTORS • • 4-WIRE SMOKE POWER DETECTORS SUPERVISION RELAY MODULE UL LISTED A77-716B COMPATIBLE CONTROL • PANEL • 2000½ EOLR ZONE TERMINALS HEAT DETECTOR Four-Wire Detector Circuit Figure 4: 4-Wire Smoke Detector Connections System Sensor System Sensor System Sensor System Sensor –...
Page 26
always enter [0] in the first space MUST Pulsing * or [TEST dF] on fixed-word keypads – 26 –...
Page 27
ALARM AUX RELAY FACTORY DEFAULTS • Set for alarm activation ( 34=1) • No zones trigger by default (Must program • 16 min. timeout( 31=4) Note: The communicator provides 12VDC power on terminal 6 when the red jumper (W3) is intact. NOTES: •...
Page 34
Master Co de P r o g r a m A lph a ? 0 = No , 1 = Ye s Cu sto m Wo r ds ? 0 = No , 1 = Ye s – 34 –...
Page 35
Summary Mode Display ZN 0 1 ZO NE 0 1 ZN 0 1 ZN 0 1 B A CK Note: ZN 0 1 BA CK ZN 0 1 BA CK O O R – 35 –...
Page 36
ZN 0 1 BA CK DO O R Note: ZN 0 1 BA CK DO O R P r o g r a m A lph a ? 0 = No , 1 = Ye s A lph a P g m If there already is a description for the zone To enter or change a description...
Page 37
alphabetic first second (refer to the CHARACTER LIST of letters, numbers, and symbols on a following page) Method 1: Method 2: – 37 –...
Page 49
MASTER SYSTEM OPERATION *This option is for future use and has not been evaluated by UL. It must be disabled ( set to "0" ; this is the default setting) –49–...
Page 51
(* Recommended) Off-Normal Test Report REFER TO THE ZONE ASSIGNMENT TABLE FOR *56 IN THE CENTERFOLD PROGRAMMING FORM . –51–...
Page 52
¯ Section 10. ALPHA DESCRIPTION PROGRAMMING Notes: In field , at the summary line for each zone, the entered values can be checked. Zone entries can be reviewed To either temporarily or permanently remove a zone from the system, –52–...
Page 53
first first second both first second first second first –53–...
Page 54
The "pulsing" option causes the bell to sound using the NFPA Three Tone Temporal Pattern ALPHA DESCRIPTION PROGRAMMING –54–...
Page 58
· · · MECHANICS OF PROGRAMMING To assign (or change) a Secondary user code, (via keypad) To delete a Secondary user code, (via keypad) Notes: –58–...
Page 66
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment. –66–...
Need help?
Do you have a question about the FA2000C and is the answer not in the manual?
Questions and answers