This manual is a step-by-step guide that will acquaint you with the system's features and benefits. It defines the components and their functions, describes their operation, and instructs you with normal and emergency procedures.
Keep this manual in a convenient place so that you can refer to it as necessary.
The First Alert Alarm System represents the latest in alarm protection technology today, including microcomputer technology to monitor all system status.
Your system is a UL Listed commercial fire alarm control/communicator. It monitors, on an around-the clock basis, the various fire alarm warning, emergency alarm warning and fire sprinkler system supervisory sensors that have been installed in your system. When the control detects an alarm, supervisory, or trouble condition, it automatically triggers an on-premises warning indication and transmits a message to a central station over the telephone line so that appropriate action can be taken.
The control features a built-in warning buzzer and LED indicators which provide the on-premises warning indication. In addition, your system may include an optional remote keypad and/or optional external alarm warning sounders which will provide additional on-premises warning indications. Please disregard references to these devices in the text that follows, if they were not installed in your system.
Your system has five protection zones. Your installer has assigned each of your system's sensing devices to one of these zones. For example, warehouse smoke detectors may have been assigned to zone 01, a fire sprinkler water valve supervisory switch may have been assigned to zone 02, etc.. If a remote keypad was installed in your system, it will display these zone numbers when an alarm, supervisory or trouble condition is detected, so that the nature and location of the fault can be pinpointed.
The fire and emergency protection portions of your system are always on and will sound an alarm if an alarm condition is detected.
When an alarm occurs, the control's buzzer, the keypad and external sounders will sound, and a message at the keypad will identify the zone(s) causing the alarm. In addition, an alarm message will be sent to the connected central monitoring station. You may stop the sound by pressing the SILENCE/RESET button at the control, or by entering the OFF sequence (user code + OFF key) at your keypad.
When an alarm, supervisory or trouble condition occurs, the keypad displays the number(s) of the zone(s) that caused the problem, and displays the type of condition present (ex. Fire, Alarm, Supv., Check). The display remains until it is cleared by entering the OFF sequence (user code + OFF key) a second time or by pressing the SILENCE/RESET button a second time if no keypad is present.
The LED indicators, SILENCE/RESET button and WARNING buzzer (shown below) are located on the control's main board inside the control's enclosure. The AC POWER, BATTERY TROUBLE, COMMUNICATION FAIL, LINE FAULT and SILENCED LED indicators are visible through a viewing window on the door of the enclosure. The enclosure door must be opened with the supplied key to gain access to the SILENCE/RESET button.
LED Indicators
AC POWER
Lights when AC power is present. Turns off when AC power is low or not present and system is operating from battery power.
BATTERY TROUBLE
Lights when battery power is low or disconnected. Turns off when battery is OK.
COMMUNICATION FAILURE
Lights when attempts to transmit a message to the central station have failed. Remains unlit when there are no problems with central station message transmission.
LINE FAULT
Lights when either the main or backup phone lines are faulted. Remains unlit when both phone lines are okay.
SILENCED
Lights when the built-in warning buzzer, the remote keypad buzzer and external alarm sounders have been silenced. Otherwise remains unlit.
Warning Buzzer | Produces slow on/off pulsing sound for fire alarms, steady sound for emergency alarms, and rapid on/off pulsing sound for supervisory and trouble conditions. |
Silence/Reset Button | Press to silence the built-in warning buzzer, the remote keypad warning buzzer and the external alarm sounder. A second press resets faulted smoke detectors and resets LED indicators if associated fault conditions have been corrected. |
Main Dialer Line Seize | Lights when control is transmitting a message to the central station on the main phone line. |
Backup Dialer LIne Seize | Lights when control is transmitting a message to the central station on the backup phone line. |
The keypads feature a telephone style (digital) keypad and a Liquid Crystal Display (LCD) which shows the nature and location of all occurrences.
The keypads feature a built-in sounder which emits the same alarm sounds as the control's built-in warning buzzer during alarm conditions.
The keypad's display screen displays the same indications as the control's built-in LED indicators, and in addition, displays the zone number of faulted zones as well as the type of fault (i.e. alarm, supervisory or trouble) present. The telephone style keypad keys allow entry of commands for silencing the warning sounds, resetting faulted smoke detectors, activating various system tests, etc.
There are two basic types of keypad displays, Alpha and Fixed-Word, either of which may have been used in your system.
Unless stated otherwise, all commands and procedures described herein apply equally to all keypads.
Typical Alpha Keypad
Fixed-Word keypads are functionally similar, except for screen displays.
When entering codes and commands, sequential key depressions must be made within 2 seconds of one another. If 2 seconds elapses without a key depression, the entry is aborted and must be repeated from its beginning.
FIXED-WORD DISPLAY
FIRE Appears when a fire alarm is detected. Accompanied by a display of the zone # in alarm.
ALARM Appears when any type of alarm is detected. "FIRE" also appears when a fire alarm is detected. Accompanied by a display of the zone # in alarm.
SUPV Appears when a fire sprinkler system supervisory condition is detected. Accompanied by a display of the zone # having the supervisory condition.
CHECK Appears when a fire zone wiring fault is detected at any time. Also appears when certain system problems such as phone line problems are detected. Accompanied by a display of the zone # in trouble.
AC Appears when AC power is present.
NO AC Appears when AC power is low, or not present. System is operating from backup battery power.
BAT Appears when backup battery is low or disconnected.
TEST Appears when the system is operating in one of its test modes (such as the fire drill test mode).
BYPASS Appears when one or more zones have been bypassed and are no longer operational.
If your system has a remote keypad installed, your installer will have programmed a 4-digit user code (known as User Number 2 code) that can be entered at your keypad to silence/reset alarms, bypass protection zones and activate the fire drill test. This code may also be used to assign up to four other user codes (known as User Number 3—6 codes).
The User Number 3—6 codes are intended for users who need limited and/or temporary control over system operation. These codes can perform the same functions as the User Number 2 code except for assigning user codes and activating the fire drill test.
User Number 2 can change, but not delete, his/her own code and can assign, change, or delete codes for User Numbers 3—6.
User Numbers 3—6 cannot assign, change, or delete user codes.
(for manually activating silent and/or audible alarms)
Your installer may have programmed the keypad's A, B, or C keys to allow manual activation of fire and/or emergency alarms. The functions that might be programmed are: Fire, Silent Emergency, Audible Emergency, and Personal Emergency.
A fire alarm sends a fire alarm message to the central station and uniquely sounds at the control and at keypad(s) and external bells and sirens. A FIRE message plus a zone number (see "Emergency Key Programmed Functions" table below) is also displayed on the keypad.
A silent emergency sends a silent alarm signal to the central station, but there is no audible alarm or visual display.
An audible emergency sends a signal to the central station and sounds a loud, steady alarm at the control and at your keypad(s) and at any external sounders that may be connected. An ALARM message plus a zone number (see "Emergency Key Programmed Functions" table) is also displayed on the keypad.
A personal emergency alarm sends an emergency message to the central station and sounds at the control and at keypad(s), but not at external bells or sirens. An ALARM message plus a zone number (see "Emergency Key Programmed Functions" table) is also displayed on the keypad.
TO MANUALLY ACTIVATE A FUNCTION AT ANY TIME OF DAY OR NIGHT
(SEE "REMOTE KEYPAD EMERGENCY KEYS" TABLE)
Press the programmed ,
, or
emergency key for at least two seconds, or alternatively, Press both keys of the corresponding
&
(A),
&
(B), or
&
(C) emergency key pair at the same time.
SEE YOUR INSTALLER AND NOTE HERE THE KEY(S) & FUNCTION(S) PROGRAMMED FOR YOUR SYSTEM
* KEY [D] ON YOUR KEYPAD IS NOT ACTIVE HERE.
Your system provides the following indications when in normal operation and there are no alarm, supervisory, or trouble conditions present:
Your system may have sensors which detect fire alarm conditions such as smoke detectors, heat detectors, sprinkler water flow sensors, etc. You system monitors these sensors 24 hours a day for continuous protection and provides a number of indications when a fire alarm condition is detected.
WHEN A FIRE ALARM CONDITION IS DETECTED, EVACUATE ALL OCCUPANTS FROM THE PREMISES IMMEDIATELY AND NOTIFY YOUR LOCAL FIRE DEPARTMENT.
Your system provides the following indications when a fire alarm condition is detected:
If your system has a keypad with a FIRE alarm emergency key, then these indications may be manually triggered by pressing this key for at least 2 seconds, (or the corresponding emergency key pair), should you become aware of a fire emergency before your detectors sense the problem.
To silence the control's buzzer, the keypad buzzer and external alarm sounders:
Press the control's SILENCE/RESET button or enter your User Code followed by the OFF key at the keypad.
The control's "SILENCED" LED lights and the keypad's LCD will display "FIRE ALARM SILENCED" (Alpha) or "SF" (Fixed-Word) to indicate that a fire alarm condition may still be present. The Alpha keypad will display the number of the zone in alarm as a Memory of Alarm indication. The fixed-word keypad alternates the zone number in alarm with the "SF" display.
To reset your system's smoke detectors and the keypad Memory of Alarm display (after heat or smoke is no longer present):
First determine and correct the cause of the fire alarm condition (e.g., fan smoke from the smoke detector chamber, reset the pull station, etc.) and then:
Press the control's SILENCE/RESET button again or re-enter your User Code plus the OFF key at the keypad.
*Except for silent alarms
Your system may have sensors which detect non-fire related alarm conditions, such as the unauthorized opening of a stock room door, the triggering of an HVAC (Heating, Ventilating, or Air Conditioning) temperature sensor, the pressing of a holdup alarm button, etc. Your system may provide some or all of the indications listed below, depending on what your installer selected to occur when one of those conditions is detected.
If your system's keypad has any active emergency alarm key(s) (see REMOTE KEYPAD EMERGENCY KEYS section) these indications may be manually triggered by pressing the appropriate emergency key.
To silence the control and keypad buzzers and external alarm sounders:
Press the control's SILENCE/RESET button or enter your User Code + the OFF key.
The keypad's LCD will display the number of the zone in alarm as a Memory of Alarm indication.
To reset the keypad alarm display and turn off the SILENCED LED at the control: First correct the cause of the alarm condition, and then:
Press the SILENCE/RESET button again or re-enter your User Code, followed by the OFF key.
Using the BYPASS Key
This feature can only be used if a remote keypad has been installed with the system. User code numbers 2-6 can only be used to bypass emergency and 24 hour non-fire protected zones.
This key is used when you want to bypass one or more zones, thus leaving them intentionally unprotected. For example, a protected stock room door can be bypassed when it is necessary to open the door without causing an alarm. To bypass an emergency zone, do the following.
All emergency zone bypasses are removed when an OFF sequence (user code plus OFF) is performed.
TYPICAL MOMENTARY DISPLAYS OF BYPASSED ZONE
If your building has a fire sprinkler system, your installer may have installed a sensor which monitors the sprinkler system (e.g., to determine whether the main water gate valve is open or that there is adequate water pressure, etc.). Your system provides the following indications when a supervisory condition is detected.
CALL YOUR INSTALLER IMMEDIATELY FOR SERVICE WHEN A SUPERVISORY INDICATION APPEARS!
To silence the control and keypad buzzers:
Press the control's SILENCE/RESET button or enter your User Code, + the OFF key
The keypad's LCD will display the number of the zone having the supervisory condition as a Memory indication.
To reset the keypad supervisory display: First have the cause of the indication corrected, and then:
Press the SILENCE/RESET button again or re-enter your User Code, followed by the OFF key.
Your system monitors each of your protection zones and various aspects of system operation for problems such as wire breaks, loss of AC power, faulted telephone lines, etc., which compromise proper alarm signaling operation. Your system provides the following indications when one of these problems is detected.
CALL YOUR INSTALLER IMMEDIATELY FOR SERVICE, WHEN ANY OF THESE INDICATIONS APPEAR FOR A CONDITION THAT CANNOT BE CORRECTED BY YOU!
To silence the control and keypad buzzers:
Press the control's SILENCE/RESET button or enter your User Code, + the OFF key.
The keypad's LCD will display the number of the zone in trouble as a Memory indication.
To reset the keypad trouble display: First have the cause of the trouble condition corrected, and then:
Press the SILENCE/RESET button again or re-enter your User Code, followed by the OFF key.
Using the Keys
This feature can be activated only while no alarm, supervisory, or trouble condition is present.
This test requires that a keypad and external fire alarm sounder be installed with the system.
Note: Only User Number 2's code can activate this test.
This test activates the external fire alarm sounders for the purpose of conducting a fire alarm drill. Your system will remain operational for fire alarm signaling while this test is active (although no message will be sent to the central station unless an actual alarm occurs).
The keypad LCD will display "FIRE DRILL ACTIVE (Alpha) or "TEST dF" (Fixed-Word) and the external fire alarm sounders will produce either a steady or a pulsing sound while this test is active, depending on what your installer selected.
To terminate the Fire Drill Test:
Enter any User Code, followed by the OFF key.
Your system will also automatically terminate this test if an alarm, supervisory or trouble condition is detected while it is activated.
FUNCTION | PROCEDURE | COMMENTS |
Silence Alarm, Supervisory or Trouble sounds | Press the SILENCE/RESET button or Enter user Code + OFF key. | SILENCED LED lights. Memory of fault remains until cleared. Keypad displays # of faulted zone. |
Reset Smoke Detectors & Displays | Press the SILENCE/RESET button a second time or Re-enter user Code + OFF key. | Will reset only if fault corrected. |
Manually Trip Emergency Alarms | Press key [A], [B], or [C] for at least 2 sec., or press keys [1]&[✱], or [✱]&[#], or [3]&[#], both at same time. | Key(s) must be enabled by installer. |
Bypass Emergency Zone(s) | To bypass , enter user code + BYPASS key + zone number(s) (use 2-digit entries). To remove bypass, enter user code + OFF key. | Bypassed zones will not cause an alarm if violated. |
Fire Drill Test | To activate: Enter User Number 2's code + # + 6 + 9. To turn off: Enter any user code + OFF key. | Activates external fire alarm sounders. |
Assign, change, or delete user code. | To assign or change : Enter User Number 2's code + CODE key + user number (2Ð6) + new code. | To delete: Enter User Number 2's code + CODE key + user number (3Ð6) and stop. |
ALPHA & FIXED-WORD DISPLAY KEYPADS
SOUND | CAUSE | DISPLAY (Fixed-Word displays are shown in parentheses) |
SLOW PULSING Keypad and, as selected by installer: ![]() ![]() |
|
|
STEADY Keypad & External |
|
|
RAPID PULSING Keypad |
|
|
One or more sensing devices will have been assigned by the installer of your alarm system to protection zones 01—05 in your system. For example, fire sensing devices may have been assigned to zone 05, air conditioning temperature sensors to zone 02, and so on.
Zone numbers 07, 95 and 96 represent Keypad "emergency" alarm functions assigned by the installer. Zone numbers 06 and 10—13 report system conditions.
This chart may be used to record the specific assignments for your system's zones 01—05, 07, 95 and 96. Your installer will assist you in recording this information.
PROTECTION ZONE DESCRIPTIONS
In the event of telephone operational problems, disconnect the control by removing the plug from the RJ31X wall jack. We recommend that your certified installer demonstrate disconnecting the phones on installation of the system. Do not disconnect the phone connection inside the control/communicator. Doing so will result in the loss of your phone lines. If the regular phone works correctly after the control/communicator has been disconnected from the phone lines, the control/communicator has a problem and should be returned for repair. If upon disconnection of the control/communicator, there is still a problem on the line, notify the telephone company that they have a problem and request prompt repair service. The user may not under any circumstances (in or out of warranty) attempt any service or repairs to the system. It must be returned to the factory or an authorized service agency for all repairs.
THE LIMITATIONS OF THIS ALARM SYSTEM
While this system is an advanced design security system, it does not offer guaranteed protection against burglary or fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons. For example:
The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This alarm system should be tested weekly to make sure all sensors and transmitters are working properly.
Wireless transmitters (used with some systems) are designed to provide long battery life under normal operating conditions. Longevity of batteries may be as much as 4 to 7 years, depending on the environment, usage, and the specific wireless device being used. External factors such as humidity, high or low temperatures, as well as large swings in temperature, may all reduce the actual battery life in a given installation. This wireless system, however, can identify a true low battery situation, thus allowing time to arrange a change of battery to maintain protection for that given point within the system.
Installing an alarm system may make one eligible for lower insurance rates, but an alarm system is not a substitute for insurance. Homeowners, property owners and renters should continue to act prudently in protecting themselves and continue to insure their lives and property.
We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves and their loved ones to learn about these developments.
Your local authorized service representative is the person best qualified to service your alarm system. Arranging a regular program with that person is advisable.
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.