5.
CAPACITY COMPENSATION RATE FOR PIPE LENGTH
AND HEIGHT DIFFERENCE
MODEL : AOU9RLFW
COOLING
Indoor unit is upper
than outdoor unit.
Height
difference H
Indoor unit is under
than outdoor unit
HEATING
Indoor unit is upper
than outdoor unit.
Height
difference H
Indoor unit is under
than outdoor unit
Indoor unit
Connection pipe
1 Indoor unit is upper than outdoor unit.
15m
49ft.
1
10m
33ft.
7.5m
25ft.
5m
16ft.
0m
0ft.
-5m
-16ft.
2
-7.5m
-25ft.
-10m
-33ft.
-15m
-49ft.
15m
49ft.
1
10m
33ft.
7.5m
25ft.
5m
16ft.
0m
0ft.
-5m
-16ft.
2
-7.5m
-25ft.
-10m
-33ft.
-15m
-49ft.
Height difference H
H
Outdoor unit
- (02 - 11) -
Pipe length
5m
7.5m
10m
16ft.
25ft.
33ft.
-
-
-
-
-
0.961
-
0.979
0.965
0.992
0.983
0.969
1.000
0.991
0.976
1.000
0.991
0.976
-
0.991
0.976
-
-
0.976
-
-
-
Pipe length
5m
7.5m
10m
16ft.
25ft.
33ft.
-
-
-
-
-
0.917
-
0.961
0.917
1.000
0.961
0.917
1.000
0.961
0.917
0.995
0.956
0.912
-
0.954
0.910
-
-
0.908
-
-
-
Outdoor unit
H
Connection pipe
2 Indoor unit is under than outdoor unit.
15m
20m
49ft.
66ft.
0.872
0.910
0.886
0.925
0.890
0.929
0.893
0.933
0.901
0.940
0.901
0.940
0.901
0.940
0.901
0.940
0.901
0.940
15m
20m
49ft.
66ft.
0.832
0.822
0.832
0.822
0.832
0.822
0.832
0.822
0.832
0.822
0.828
0.818
0.826
0.816
0.824
0.814
0.815
0.805
Indoor unit