(6)-2 Rule of settng address
Unit
PWFY unit
Standard indoor unit
Outdoor unit
BC controller
(Main)
BC controller
(Sub)
ME, LOSSNAY
Remote controller
(Main)
ME, LOSSNAY
Remote controller
(Sub)
Group remote
controller
System remote
controller
ON/OFF remote
controller
G-50A
GB-50A
AG-150A
LMAP02-E
Note1: To set the address to "100", set it to "50"
Note2: Outdoor units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending
order of their address.
Address setting
Example
01 ~ 50
51 ~ 99, 100
(Note1)
52 ~ 99, 100
53 ~ 99, 100
1
101 ~ 150
Fixed
1
151 ~ 199, 200
Fixed
2
201 ~ 250
Fixed
000, 201 ~ 250
100
000, 201 ~ 250
100
0,2
000, 201 ~ 250
100
2
201 ~ 250
Fixed
Use the most recent address within the same group of
indoor units. Make the indoor units address connected
to the BC controller (Sub) larger than the indoor units
address connected to the BC controller (Main).
If applicable, set the sub BC controllers in an PURY
system in the following order:
(1) Indoor unit to be connected to the BC controller (Main)
10
1
(2) Indoor unit to be connected to the BC controller (No.1 Sub)
(3) Indoor unit to be connected to the BC controller (No.2 Sub)
Set the address so that (1)<(2)<(3)
The smallest address of indoor unit in same refrigerant
system + 50
Assign sequential address numbers to the outdoor
units in one refrigerant circuit system. OC and OS are
automatically detected. (Note 2)
10
1
Please reset one of them to an address between 51
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"
The address of outdoor unit + 1
Please reset one of them to an address between 52
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
10
1
as "01~ 50"
Lowest address within the indoor units connected to
the BC controller (Sub) plus 50.
10
1
The smallest address of indoor unit in the group + 100
The place of "100" is fixed to "1"
10
1
The address of main remote controller + 50
The address automatically becomes "200" if it is set
as "00"
10
1
The smallest group No. to be managed + 200
10
1
10
1
10
1
0~5
0~9
10
1
10
1
- 46 -