Status Code 25 - Model Selection Or Setup Error - Bryant 355CAV A Series Troubleshooting Manual

Variable speed, step-modulating electronic condensing four-way multipoise gas furnace
Hide thumbs Also See for 355CAV A Series:
Table of Contents

Advertisement

Status Code 25
MODEL SELECTION OR SETUP ERROR – If status code 25 only flashes 4 times on power-up the variable speed furnace
control is missing its model plug (PL4) and is defaulting to the model selection stored in memory.
If status code 25 flashes continuously it could indicate any of the following:
1.
Model plug (PL4) is missing and there is no valid model stored in permanent memory. This will happen if you forget to
install the model plug (PL4) on a service replacement board.
2.
Thermostat call with SW1-1 ON.
3.
Thermostat call with SW1-6 ON.
4.
SW1-1 and SW1-6 both ON together.
5.
Two different furnace models twinned.
6.
Board does not recognize model plugs HK70EZ017 – 021. Board software version V12 or later required.
STEP
1.
Turn power off, remove the blower access panel, and disconnect User Interface ABCD
connector (if used) or the R thermostat lead (if used) from the furnace control board.
2.
Turn power on and depress door switch. Use a piece of tape to hold switch closed.
3.
Does status code 25 flash only 4 times on power-up?
4.
The model plug is missing or invalid but the control will default to the model stored in
memory. The furnace will operate properly as if the model plug was installed. If you have the
APM program you can confirm the setting in memory.
5.
Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS.
6.
Is setup switch SW1-1 in the ON position?
7.
Put setup switch SW1-1 in the OFF position.
8.
Is setup switch SW1-6 in the ON position?
9.
Put setup switch SW1-6 in the OFF position.
10.
Is this a new service replacement control?
11.
You need to remove the model plug PL4 from the old control and install it on the new
replacement control. Once you install the model plug the power to the furnace needs to be
reset because the model plug is only read on power-up.
12.
If the model plug is not available from the old control, reference the model plug chart on the
wiring schematic for the correct part number. If absolutely necessary you can install two
resistors into the PL4 connection on the control board. R1 goes across the middle 2 pins and
R2 goes across the outer 2 pins. Reference the model plug chart on the schematic for the
correct resistance values. Resistors can be purchased at a nearby Radio Shack. The resistors
need to be within 10% of the stated value. Check with an ohm meter before installing.
13.
Is this furnace twinned with another furnace?
14.
Is the MAIN furnace flashing the status code?
15.
Do the furnaces have the same model number on the rating plate?
16.
Replace one of the furnaces because you cannot twin different size furnaces.
17.
Replace the variable speed furnace control.
18.
One of the model plugs is bad. Ohm out each one and replace the one that does not match the
model plug chart on the wiring schematic.
19.
Is the model plug PL4 from the old control installed?
20.
Make sure you have installed a furnace control with version V12 or later software installed.
The version of software is printed in the WHITE box near the L2 terminals on the right side of
the furnace control. The majority of older controls will not have a software version printed on
the control. Reference Figure 1 in Appendix A for the location of the software version.
ACTION
- 21 -
YES
NO
GO TO
2
3
4
6
5
INDEX
7
8
5
9
10
5
19
13
12
5
14
17
15
17
18
16
5
5
5
20
11
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents