6 Commissioning
Slide the switch until the "I" symbol
appears.The display and operating
mode indicator light up: the boiler is
ready to run.
Open the isolating valves located on
the pipes: they will be placed in the
direction of the flow.
Open the auto air vent on the pump as
well as the automatic bleeders of the
system.
Open the two blue filling loop valves
situated under the boiler simultaneously
until you obtain a 2 bar pressure on the
indicator.
Bleed each radiator to remove the air,
re-tighten bleed screws.
Leave the cap on the pump auto air
vent open.
Flush the domestic hot water system by
openning the hot water taps for several
minutes.
Make sure the display indicates a
system pressure of between 1 and 2
bars. Re-fill system as necessary.
Operate the appliance for at least 15
minutes on heating with a heating
temperature equal or greater to 50°C.
Flush the domestic hot water system by
openning the hot water taps for several
minutes.
Make sure the display indicates a
system pressure of between 1 and 2
bars. Re-fill system as necessary.

7 Specific adjustments

7.1

Heating circuit adjustment

This flow rate will be adjusted according to
the system calculations.
When it is delivered, the (1) integrated
bypass screw is open by half a turn.
1
Legend
1
Bypass screw
Depending on the requirements, adjust
this screw (for example, screw for
closing) in order to fit the available
pressure head to the system energy
loss according to the output/pressure
curve.
1
2
Legend
1
Speed selector of pump
2
Speed I
3
Speed II
Turn the selector (1) to choose pump
speed I or II in relation to the output/
pressure curve.
28
3