Huawei NetCol5000-A020 User Manual page 30

Air cooled in-row precision air conditioner
Table of Contents

Advertisement

NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
Support Preparations
A support is optional for the air conditioner. You can configure a support in the following two
ways:
Adjust the height of the support according to the actual
dimensions for reference.
Figure 3-5 Support dimensions (unit: mm)
Make supports by referring the following recommendations:
1.
Issue 01 (2014-06-30)
Prepare the support according to the drawings obtained from Huawei.
Specify the support as a mandatory item for the air conditioner in the contract.
Figure 3-5
shows the support dimensions of the air conditioner which installed the
enclosure increasing the depth to 1200 mm.
If not configured the enclosure. The size of the depth 1143 mm and 1200 mm all subtract
200 mm when making support.
Recommended to use angle steel, square steel or channel steel, and width is 45–60 mm,
thickness is 4–5 mm.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Installation Guide
situation.Figure 3-5