Procedure
Step 1 Tap Shutdown on the main menu, switch off the main circuit breaker QF1 and the front end
circuit breaker.
Step 2 Lever the solenoid coil in the liquid solenoid valve using the flat screwdriver, and pull the
solenoid coil together with the junction box out of the cabinet.
Step 3 Remove bolts using the Phillips screwdriver and pull out the junction box. Install the new
solenoid coil and secure bolts.
Step 4 Fix the solenoid coil onto the sleeve using bolts.
Step 5 Install the air filters and rear door if no problem is found.
----End