Huawei NetCol5000-A020 User Manual page 21

Air cooled in-row precision air conditioner
Table of Contents

Advertisement

NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
Item
Filter level
Dimensions (H x W x D)
Net weight/Gross weight
If the equipment room does not have requirements for humidity, air conditioners that do
not have humidification function or have partial humidification function are
recommended.
When the total load of servers is less than 30% load of a single air conditioner, the
humidity might be relatively high. In this case, contact Huawei technical support.
Table 2-6 Optional parameters
Item
Maximum
current
Input power
Voltage
tolerance
Frequency
tolerance
Heating
Humidification
a: Recommended to add the voltage regulator in the front end if the power exceeds this
range. Otherwise, air conditioner will generate frequency alarms and cannot run.
Issue 01 (2014-06-30)
Specifications
NetCol5000-A
020
HM13N10020
E0
16.5 A
380–415 V AC
50 Hz 3W + N
+ PE
Rated
a
voltage± 10%
Rated
frequency± 3 Hz
None
None
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Specifications
G3
2000 mm x 300 mm x 1000 mm
230 kg/275 kg
NetCol5000-A
020
HM13N1E120
E0
23 A
380–415 V AC
50 Hz 3W + N
+ PE
Rated
voltage± 10%
Rated
frequency± 3 Hz
Configured
Configured
2 Product Description
NetCol5000-A
NetCol5000-A
020
020
HQ13N10020
HQ13N1E120
E0
E0
16.5 A
23 A
380 V AC 60
380 V AC 60
Hz 3W + N +
Hz 3W + N +
PE
PE
Rated
Rated
voltage± 10%
voltage± 10%
Rated
Rated
frequency± 3 Hz
frequency± 3 Hz
None
Configured
None
Configured
14