Fujitsu AS* A09LEC Service Instruction page 35

Split type room air conditioner wall mounted type
Table of Contents

Advertisement

Trouble shooting 8
OUTDOOR UNIT Error Method:
Outdoor Temperature Thermistor Error
Detective Actuators:
Outdoor unit Main PCB
Outdoor temperature thermistor
Forecast of Cause :
1. Connector connection failure
Check Point 1 : Check connection of connector
Check if connector is removed.
Check if connector is erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
Temperature
(°C )
Resistance value (k )
Temperature
(°C )
Resistance value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
OK
Check Point 3 : Check voltage of Inverter PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
BLACK
1
1
BLACK
2
2
CN71
BLACK
3
3
BLACK
4
4
BLACK
1
1
CN70
2
2
BLACK
3
3
If the voltage does not appear, replace Main PCB.
Indicate or Display:
Refer to error code table.
Detective details:
When Outdoor temperature thermistor open or short-circuit
is detected at power ON or while running the compressor.
2. Thermistor failure
-30
-20
-10
224.3
115.2
62.3
20
30
40
12.6
8.0
5.2
THERMISTOR
( HEAT EXCHANGER )
THERMISTOR
( DISCHARGE PIPE )
THERMISTOR
( OUTDOOR TEMP. )
3. Inverter PCB failure
-5
0
5
10
46.6
35.2
26.9
20.7
50
60
70
80
3.5
2.4
1.6
1.2
02-10
15
16.1