Fujitsu AS* A09LEC Service Instruction page 23

Split type room air conditioner wall mounted type
Table of Contents

Advertisement

3. ANTIFREEZING CONTROL (Cooling and Dry mode)
The compressor speed is decreased on cooling & dry mode when the indoor heat exchanger
temperature sensor detects the temperature lower than
Then, the anti-freezing control is released when it becomes higher than Release temperature A.
(Table 22 : Anti-freezing protection operation / Release temperature)
Outdoor temperature zone
A, B , C, D
4. COOLING PRESSURE OVERRISE PROTECTION
When the outdoor unit heat exchange sensor temperature rises to
the compressor is stopped.
Then the compressor will be restarted after 3 minutes ST.
5. HIGH TEMPERATURE RELEASE CONTROL ( HEATING MODE )
In heating mode, the compressor speed is controlled based on the detection value
of the indoor heat exchanger temperature sensor.
5-1. HIGH TEMPERATURE RELEASE CONTROL of Outdoor Unit
[ Control System ]
Indoor heat exchange
temperature rises
The compressor speed is
decreased 3rps every 60seconds.
53°C
It returns to the normal operation
5-2. HIGH TEMPERATURE RELEASE CONTROL of Indoor Unit
[ Control System ]
Indoor heat exchange
temperature rises
55°C
It returns to the normal operation
[ ASYA09LEC ]
Compressor operation
57rps or more
35 ~ 55rps
28 ~ 33rps
18 ~ 23rps
[ ASYA12LEC ]
Compressor operation
48rps or more
39 ~ 45rps
27 ~ 36rps
18 ~ 25rps
Release temperature A
E, F
Refer to below
55rps
Rotational speed down every 120 sec
23rps
OFF
45rps
Rotational speed down every 120 sec
25rps
OFF
4°C
.
7°C
13°C
67°C
Indoor heat exchange
temperature drops
50°C
Indoor heat exchange
temperature drops
52°C
01-20