Operating Instructions; Programming Boiler Settings - Westinghouse WBRE80 User Manual

Premier high efficiency boilers
Table of Contents

Advertisement

ENTER – The ENTER key is used to access parameter
programming mode. To access this mode, hold down the
ENTER key for more than 4 seconds. The readout will change
to:
ENTER MENU CODE
000
One of the zeroes will be blinking. Use the ^ v arrow keys to
change the blinking digit to the correct value. Use the < >
arrow keys to select the next digit to change and again use the
^ v keys to change the value. Repeat until the correct code is
entered. Press the ENTER key to accept the code entered. If
the code is correct, the readout will change to the appropriate
screen. If the programming code is not accepted, the readout
will continue to display as shown above.
ENTER is also used to enable a function for editing. After the
user navigates to the desired function, the user holds down
ENTER for one second. When ENTER is released, the function
value will begin to blink. The function can now be changed
using the ^ v keys. After the new value is displayed, the user
then presses ENTER for 1 second to lock the new value of the
function. The value will then stop blinking.
LEFT AND RIGHT ARROW KEYS – < > are used to navigate
between the default display, status display, analog and
cascade displays if they are enabled. The < > keys are also used
in programming modes to change between programmable
functions. It is recommended you use the Menu Maps in
the back of this manual and the detailed menu instructions
printed in this section to help in menu navigation.
UP AND DOWN ARROW KEYS – ^ v are used to navigate
between the various functions displayed in the menu. After
the function is enabled for editing by pushing the ENTER
key, the ^ v keys are used to adjust the function upward or
downward to the desired value.
C. Operating Instructions
Before operating the unit, it is important to remove the cover
and verify that the gas line and water lines are connected to
boiler and fully purged. If you smell gas, STOP; Follow the
safety instructions listed in the first part of this section. If you
do not smell gas, follow the next steps.
1. Turn down the thermostats before applying power to the
boiler. If 0–10 volt or other inputs are used, make sure that
they are set so there is no call for heat while programming.
2. Turn on the power to the boiler or boilers if a cascade system
used.
3. Next, check the boiler settings. Adjustment and factory
defaults are outlined within this section. If a cascade system
is used, it is important that all the boilers have the same boiler
settings.
4. Next, check the system settings. Adjustments and factory
defaults are outlined within this section. If a cascade system
is used, it is important that the Master Boiler is programmed
with the correct system settings.
5. Create a demand on the boiler or boilers if a cascade system
is used. The user can monitor system functions when the
boilers are operational.
6. If the boilers fail to start, refer to the troubleshooting
section in the back of this manual.
D. Programming Boiler Settings
Boiler Setting Program Access
Note: Programming the boiler control is not possible when the
boiler is firing. Make sure any input which can create a demand
on the boiler, such as the tank thermostat, is turned off, so the
boiler will remain idle to allow programming.
Screen
ENTER MENU CODE
000
ENTER MENU CODE
600
Table 15 - Boiler Setting Access
Boiler Setting Program Navigation
Once the code is confirmed, the user can start to set the Boiler
Settings. Use the arrow keys on the display to navigate through
the Boiler Settings. A blinking setting indicates the setting can
be changed. To change a setting, press ENTER. Boiler settings
can be increased by pressing ^ and decreased by pressing v on
the display. When done, press ENTER. The setting will stop
blinking and the user can move on to next setting. Press RESET
to exit programming and store settings. Listed below are the
boiler settings that can be programmed into the control.
Screen
CENTRAL HEAT
o
180
F
CENTRAL DIFF SET
o
30
F
DHW SETPOINT
o
119
F
DHW DIFF SETPOINT
o
7
F
TEMP DISPLAY C OR F
o
F
Table 16 - Boiler Setting Program Navigation
Clock Settings
(NOTE: The clock will reset if the boiler is powered off for more
than a week.)
Screen
CLOCK MODE
(12/24)
08/28/2009
Fr 9:42A
Description
To access the boiler setting program,
press and hold ENTER for 4 seconds
until the display shows the screen at
left.
Use the arrow keys to log in the
Boiler Menu Access Code - 600.
Press ENTER to confirm the code
and access the Boiler Setting
Program navigation menu.
Description
Allows the user to adjust the boiler
o
set point from 50F to 190
F (Factory
o
Default 180
F).
Adjusts the boiler differential set
o
o
point from 5
F to 30
F (Factory
o
Default 30
F).
Adjusts the indirect tank set point
o
o
from 70
F to 185
F (Factory Default
o
119
F).
Adjusts the DHW differential set
o
o
point from 1
F to 30
F (Factory
o
Default 7
F).
Adjusts
the
temperature
measurement in F = Fahrenheit
to C = Celsius (Default is
Fahrenheit).
Description
Changes the clock from 12 hour
mode (8:45 PM) to 24 hour mode
(20:45). To change to 24 hour mode,
press ENTER. The letter (A or P)
after the time will blink. Press the
up or down arrow key once and the
letter will disappear. Press ENTER to
save the new setting.
WHL-052 Rev. 4.28.16