22 CONDENSATE DRAIN

Front View
155mm
23 CONDENSATE PIPE TERMINATION CONFIGURATIONS
Note. ALL EXTERNAL PIPE RUNS MUST BE IN ACCORDANCE WITH BS6798
1. INTERNAL TO SINK WASTE
UPSTREAM OF SINK WASTE
TRAP
2. INTERNAL TO SINK WASTE
DOWNSTREAM OF SINK
WASTE TRAP (PREFERRED
METHOD)
22
INSTALLATION
Side View
Condensate
drain
BOILER
cla7771b
Air Break
cla9252
Before mounting the boiler on the wall, the condensate
drain (provided in the h/ware pack) must be connected
from the boiler 'S' trap to a drainage point, preferably
within the building.
Ensure that the condensate trap is full of water before
commissioning the boiler. Refer to Frame 25.
The routing of the drain must be made to allow a
minimum fall of 1 in 20 away from the boiler, throughout
its length.
The drainage pipework must be arranged so that
obstruction (e.g. through freezing) of external drainage
pipe does not give rise to spillage within the dwelling.
IMPORTANT.
If excessive external pipework cannot be avoided, an
additional siphon kit and insulation are recommended,
in order to prevent possible freezing.
All pipework and fittings in the condensate drain system
must be made of plastic. No other materials may be
used.
The drain outlet on the boiler is standard 21.5 mm
overflow pipe. This size must not be reduced in any part
of its length.
If external condensate pipe run is greater than 3m then
pipe must be 32mm nominal diameter. Consideration
must be given to insulating external condensate pipe
runs.
Sink constitutes
air break
Sink
75mm trap
Open end of pipe
direct into gulley
below grating but
above water level
DRAIN
Open end of pipe
direct into gulley
below grating but
above water level
Ground Level
DRAIN
icos system -
Installation and Servicing
Ground Level
continued . . . .