Ferroli optima 2001 VMF7 Installation Instructions Manual page 31

Wall mounted, room sealed, fan assisted, gas condensing combination boiler
Table of Contents

Advertisement

Details Burner
Fig. 33
2.0
FLOWMETER (Domestic Hot Water) AND FILTER
a)
Refer to section 1, items a, b, c, d, f and g (drain D.H.W. only fig. 34).
b)
Undo the flow switch unions and carefully lower the flow switch taking care not to lose either the (three) sealing washers,
filter or flow restrictor.
c)
Disconnect the electrical connections to the flowmeter.
d)
Re-assemble in reverse order, ensuring that the filter, flow restrictor and sealing washers are in the correct position
(fig. 35). The polarity for the electrical wiring is immaterial.
Union to be released when
removing heat exchanger
C.H. temperature thermometer
phial and shim
C.H. pressure
D.H.W.
relief valve
drain point
(drain point)
Fig. 34
2001
Key
81. Ignition electrode
82. Flame sensing electrode
Heat exchanger
venting cap
C.H. pressure
sensing point
37
37 Cold water inlet filter
136 Flowmeter
39 Cold water flow restricter
136
39
Caleffi
Fig. 35
31