Heatilator ODYSSEY ODY42 Installation & Operating Instructions Manual page 20

Radiant fireplace with factory installed gas log set
Table of Contents

Advertisement

2. Installing a Termination Cap on a Chase Enclosed
Chimney
Construct a chase of desired materials maintaining a
minimum 2” air space around the chimney.
Install the chimney sections up through the chase
enclosure. When using a round termination cap (TR344),
the uppermost top flashing section of pipe must extend
above the top of the chase collar to allow installation of
the storm collar and termination cap.
For installations utilizing a telescoping round termination
cap (TR342), the uppermost chimney section must be
below the top of the chase top, but not more than 14½”
below the top of the chase top flashing collar. See
Figure 21.
For installations utilizing a square termination cap
(ST375), the last chimney section must not be more than
4¾” below the chase top.
When installing a TS345 square termination, the
uppermost chimney section must be no less than 3”
below the top of the chase top or more than 2” above the
top of the chase top.
Attach the chase top (CT35) to the top of the chase.
Install the termination cap, using the instructions provided
with it.
20
ODYSSEY SERIES FIREPLACE WITH GAS LOG SET
WARNING!
WARNING!
31818 Rev J
WARNING!
01/04