Honeywell DT8035 Dual Tec Installation Instructions page 3

Motion sensor

Advertisement

1. Close the sensor and apply power to the sensor. Initialization is complete when the LED stops flashing slowly
(about 30 seconds).
2. Walk through the detection area and observe the LED.
3. Adjust the microwave range as necessary to meet installation requirements.
Walk test mode is active for 10 minutes, then automatically exits test mode, disables the LED and enters normal
operation mode. For an additional 10 minute walk test, enable Walk Test mode again with the Flashlight feature:
Note: In Walk Test mode the LED is active regardless of the LED Enable/Disable Dip switch setting.
Flashlight Feature:
1. Use a flashlight with a bright light beam, and stand within 4' (1.2 m) of the sensor.
2. Swing past the light beam across the sensor IR window 3-5 times, holding the beam
on the window for 0.5 second each pass.
The flashlight feature is only available for the first 24 hours after installation.