If the unit is to be installed in an attic, the passageway to and the service area around the unit must have flooring.
To ensure proper furnace operation, install, operate and maintain the furnace in accordance with these installation and
operation instructions, all local building codes and ordinances. In their absence, follow the latest edition of the National Fuel Gas
Code (NFPA 54/ANSI Z223.1), and/or CAN/CSA B149 Installation Codes, local plumbing or waste water codes, and other applicable
codes.
A copy of the National Fuel Gas Code (NFPA 54/ANSI Z223.1) can be obtained from any of the following:
American National Standards Institute
25 West 43rd Street, 4th Floor
New York, NY 10036
The rated heating capacity of the furnace should be greater than or equal to the total heat loss of the area to be heated. The total heat
loss should be calculated by an approved method or in accordance with "ASHRAE Guide" or "Manual J-Load Calculations" published by
the Air Conditioning Contractors of America.
CSA International • 178 Rexdale Boulevard • Etobicoke, Ontario, Canada M9W 1R3
L
R
OCATION
EQUIREMENTS
Follow the instructions listed below and the guidelines provided in the Combustion and Ventilation Air Requirements section when
selecting a furnace location.
T
O PREVENT POSSIBLE EQUIPMENT DAMAGE
,
PERSONAL INJURY OR DEATH
OBSERVED WHEN INSTALLING THIS UNIT
Centrally locate the furnace with respect to the proposed or existing air distribution system.
Ensure the temperature of the return air entering the furnace is between 55°F and 100°F when the furnace is heating.
Provide provisions for venting combustion products outdoors through a proper venting system. Special consideration should
be given to vent/flue pipe routing and combustion air intake pipe when applicable. Refer to Vent/Flue Pipe and Combustion
Air Pipe -Termination Locations for appropriate termination locations and to determine if the piping system from furnace to
termination can be accomplished within the guidelines given. NOTE: The length of flue and/or combustion air piping can
be a limiting factor in the location of the furnace.
Locate the furnace so condensate flows downwards to the drain. Do not locate the furnace or its condensate drainage
system in any area subject to below freezing temperatures without proper freeze protection. Refer to Condensate Drain
Lines and Trap for further details.
Ensure adequate combustion air is available for the furnace. Improper or insufficient combustion air can expose building
occupants to gas combustion products that could include carbon monoxide. Refer to Combustion and Ventilation Air
Requirements.
Set the furnace on a level floor to enable proper condensate drainage. If the floor becomes wet or damp at times, place the
furnace above the floor on a concrete base sized approximately 1-1/2" larger than the base of the furnace. Refer to the
Horizontal Applications and Considerations for leveling of horizontal furnaces.
Ensure upflow or horizontal furnaces are not installed directly on carpeting, or any other combustible material. The only
combustible material allowed is wood.
A special accessory subbase must be used for upright counterflow unit installations over any combustible material (including
wood). Refer to subbase instructions for installation details. (NOTE: A subbase will not be required if an air conditioning coil
is located beneath the furnace between the supply air opening and the combustible floor.
Exposure to contaminated combustion air will result in safety and performance-related problems. Do not install the furnace
where the combustion air is exposed to the following substances:
permanent wave solutions
carbon tetrachloride
deicing salts or chemicals
cleaning solutions (such as perchloroethylene)
National Fire Protection Association
A copy of the CAN/CSA B149 Installation Codes can also be obtained from:
& C
ONSIDERATIONS
WARNING
,
PROPERTY DAMAGE
THE FOLLOWING BULLET POINTS MUST BE
.
chlorinated waxes or cleaners
water softening chemicals
halogen type refrigerants
1 Batterymarch Park
Quincy, MA 02169-7471
P
OSSIBLE PROPERTY DAMAGE
,
,
FIRE
EXPLOSION
OR CARBON MONOXIDE MAY RESULT FROM IMPROPER INSTALLATION
REPAIR OPERATION
6
CSA International
8501 East Pleasant Valley
Independence, OH 44131
WARNING
,
PERSONAL INJURY OR DEATH DUE TO
,
,
,
SMOKE
SOOT
CONDENSATION
,
OR MAINTENANCE OF THIS PRODUCT
chlorine-based
swimming pool chemicals
printing inks
,
ELECTRICAL SHOCK
,
.