Drainage system. Check for blockage and/or leakage. Check hose connections at and internal to furnace.
Wiring. Check electrical connections for tightness and/or corrosion. Check wires for damage.

Filters.

F
ILTERS
F
M
ILTER
AINTENANCE
Improper filter maintenance is the most com-
mon cause of inadequate heating or cooling
performance. Filters should be cleaned (per-
manent) or replaced (disposable) every two
months or as required. When replacing a fil-
ter, it must be replaced with a filter of the
same type and size.
F
R
ILTER
EMOVAL
Depending on the installation, differing filter
arrangements can be applied. Filters can be
installed in either the central return register
or a side panel external filter rack (upflow only).
A media air filter or electronic air cleaner can
be used as an alternate filter. Follow the filter
sizes given in the Recommended Minimum Fil-
ter size table to ensure proper unit perfor-
mance.
To remove filters from an external filter rack in an upright upflow installation, follow the directions provided with external filter rack
kit.
H
U
F
R
ORIZONTAL
NIT
ILTER
EMOVAL
Filters in horizontal installations are located in the central return register or the ductwork near the furnace.
To remove:
1. Turn OFF electrical power to furnace.
2. Remove filter(s) from the central return register or ductwork.
3. Replace filter(s) by reversing the procedure for removal.
4. Turn ON electrical power to furnace.
M
A
F
E
EDIA
IR
ILTER OR
LECTRONIC
Follow the manufacturer's directions for service.
B
URNERS
Visually inspect the burner flames periodically during the heating season. Turn on the
furnace at the thermostat and allow several minutes for flames to stabilize, since any
dislodged dust will alter the flames normal appearance. Flames should be stable, quiet,
soft, and blue (dust may cause orange tips but they must not be yellow). They should
extend directly outward from the burners without curling, floating, or lifting off. Flames
must not impinge on the sides of the heat exchanger firing tubes.
DIAGNOSTIC CODES
1 flash, then pause
2 flashes, then pause
3 flashes, then pause
4 flashes, then pause
5 flashes, then pause
6 flashes, then pause
7 flashes, then pause
8 flashes, then pause
Continuous flashing
OFF
ON
The LED will also flash once at power-up.
A
C
R
IR
LEANER
EMOVAL
System lockout
Pressure switch stuck closed
Pressure switch stuck open
Open limit switch
Flame has been sensed when no flame
should be present (no call for heat)
Open rollout switch / open control board fuse
Low flame sense signal
Igniter relay fault
115 Volt AC power reversed
Control failure
Normal operation
40
Burner Flame
Figure 43