Address Setting - Toshiba MCY-MAP0401HT Installation Manual

Multi type
Hide thumbs Also See for MCY-MAP0401HT:
Table of Contents

Advertisement

Regulation of high frequency wave
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc (*1)
at the interface point between the user's supply and the public system. It is the responsibility of the installer or user of the
equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected
only to a supply with a short-circuit power Ssc greater than or equal to Ssc (*1)
Furthermore, when similar equipment or other equipment which may cause harmonic current emissions are to be
connected to the same interface point with this equipment, to reduce the risk of possible problems which may be caused
from addition of those harmonic current emissions, it is recommended to make sure that the short-circuit power Ssc at the
interface point is greater than the sum of the minimum Ssc required by all the equipment which will be connected to the
interface point.
Ssc (*1)
Model
Ssc (kVA)
MCY-MAP0401HT (Z) (ZG)
MCY-MAP0501HT (Z) (ZG)
920
MCY-MAP0601HT (Z) (ZG)
33-EN
– 17 –
8

Address setting

In this air conditioner, it is necessary to set up the indoor address before starting the operation. Set up the
address in the following procedure.
CAUTION
1. Set up the address after the wiring work has been completed.
2. Be sure to turn on the power in order of indoor unit → outdoor unit. If turning on the power in the reverse order,
a check code [E19] is displayed. When a check code is displayed, turn on the power again.
3. It requires a maximum of 10 minutes (Usually, approx. 5 minutes) to automatically set-up an address for 1
system.
4. To set up an address automatically, the set-up of the outdoor unit needs to be completed.
(Address setup cannot be performed by power-ON only.)
5. To set up an address, the air conditioner does not need to be in operation.
6. Manual address setup is also available besides automatic setup.
Automatic address
: Setup from SW15 on the interface P.C. board of the outdoor unit
Manual address
: Setup from the wired remote controller
* It is temporarily necessary to set-up the indoor unit as a 1:1 using a wired remote controller.
Automatic Address Setup
Without central control : To the address setup procedure 1
With central control
: To the address setup procedure 2
(However, go to the procedure 1 when the central control is performed in a single refrigerant system.)
(Example)
In case of central control in a single refrigerant system In case of central control over refrigerant system
Address setup procedure
Wire systematic diagram
Outdoor
Central remote
controller
Indoor
Indoor
Remote
Remote
controller
controller
◆ Address setup procedure 1
1
Turn on power of indoor / outdoor units.
(In order of indoor → Outdoor)
2
After approx. 1 minute, check that
is displayed in 7-segment display section on the interface
P.C. board of the outdoor unit.
3
Press SW 15 to start the automatic address setting.
(Max. 10 minutes for 1 line (Usually, approx. 5 minutes))
4
Auto 1 → Auto 2 → Auto 3
When the count
in 7-segment display section, and it changes from
U. 1. - - - (U. 1. flash)
to
U. 1. - - - (U. 1. light)
setup finished.
5
When perform a central control, connect a relay
connector between [U1U2] of the outdoor unit and
[U3U4] terminals.
To procedure 1
To procedure 2
Outdoor
Outdoor
Central remote
controller
Indoor
Indoor
Indoor
Indoor
Remote
Remote
Remote
controller
controller
controller
Interface P.C. board
SW04
SW05 SW15
U. 1. L08 (U. 1. flash)
D600 D601 D602 D603 D604
SW01
SW02 SW03
1
1
is displayed
, the
5
Relay connector
U1
For control
wiring between
indoor and
outdoor
Outdoor
Central remote
controller
Indoor
Indoor
Remote
controller
3
2, 4
1
U2
U3
U4
For wiring of
central control
system
34-EN