Selection Of Installation Place - Toshiba MCY-MAP0401HT Installation Manual

Multi type
Hide thumbs Also See for MCY-MAP0401HT:
Table of Contents

Advertisement

4

Selection of installation place

Upon customer's approval, install the air conditioner in a place which satisfies the following conditions:
• Place where it can be installed horizontally.
• Place which can reserve a sufficient service space for safe maintenance or checks.
• Place where there is no problem even if the drained water overflows.
Avoid the following places:
• Salty places (seaside area) or places with much gas sulfide (hot spring area) (If selecting such a place, special maintenance
is required.)
• Places where oil (including machine oil), steam, oil smoke or corrosive gas is generated.
• Places where iron or other metal dust is present. If iron or other metal dust adheres to or collects on the interior of the air
conditioner, it may spontaneously combust and start a fire.
• Places where an organic solvent is used.
• Chemical plants with a cooling system using liquid carbon dioxide.
• Places where a device generating high frequency (inverter, non-utility generator, medical apparatus, or communication
equipment) is set. (Malfunction or abnormal control of the air conditioner, or interference to devices listed above may occur.)
• Places where discharged air from the outdoor unit blows against the windows of a neighbour's house.
• Places unable to bear the weight of the unit.
• Places with poor ventilation.
9-EN
– 5 –
Installation place
Considering functions, reserve space necessary for
installation work and servicing.
• A place which provides a specified space around the
outdoor unit.
• A place where the operation noise and discharged air are
not given to your neighbors.
• A place that is not exposed to a strong wind.
• A place that does not block a passage.
• When the outdoor unit is installed in an elevated position,
be sure to secure its feet.
• There must be sufficient space for carrying in the unit.
• A place where the drain water does not make any problem.
CAUTION
1. Install the outdoor unit at a place where discharge air
is not blocked.
2. When an outdoor unit is installed in a place that is
always exposed to a strong wind like a coast or on a
high story of a building, secure a normal fan
operation by using a duct or a wind shield.
3. When installing the outdoor unit in a place that is
constantly exposed to a strong wind such as the
upper stairs or rooftop of a building, apply the
windproof measures referring to the following
examples.
1)Install the unit so
500 mm
that its discharge port
faces to the wall of
the building. Keep a
distance 500 mm or
more between the
unit and the wall
surface.
2) Supposing the wind direction during the
operation season of the air conditioner, install the
unit so that the discharge port is set at right angle
to the wind direction.
Strong Wind
Strong Wind
4. Installation in the following places may result in
some troubles. Do not install the unit in such places
below.
• A place full of machine oil.
• A place full of sulfuric gas.
• A place where high-frequency radio waves are
likely to be generated as from audio equipment,
welders, and medical equipment.
Necessary space for installation
◆ Obstacle at rear side
Upper side is free
1. Single unit installation
2. Obstacles at both right and left sides.
The height of the
obstacle should be
lower than the height
of the outdoor unit.
150
300
or more
or more
3. Serial installation of two or more units
150
300
300
300
or more
or more
or more
or more
The height of the obstacle should be lower
than the height of the outdoor unit.
Obstacle also at the upper side
150
or more
◆ Obstacle at front side
Upper side is free
1. Single unit installation
2. Serial installation of two or more units
10-EN