2. When you want to know position of the indoor unit using the address
• To confirm the unit numbers in a group control;
[Procedure] (Operation while the air conditioner stops)
The indoor unit numbers in a group control are successively displayed, and the corresponding indoor fan is turned on.
1
VENT
TEST
Push
+
buttons simultaneously for
4 seconds or more.
• Unit No
is displayed.
• The fans of all the indoor units in a group control are
turned on.
2
Every pushing
button, the indoor unit
numbers in the group control are successively
displayed.
• The firstly displayed unit number on number indicates
the address of the header unit.
• Only fan of the selected indoor unit is turned on.
3
TEST
Push
button to finish the procedure.
All the indoor units in group control stop.
▼ To confirm all the unit numbers from an arbitrary wired remote controller;
[Procedure] (Operation while the air conditioner stops)
The indoor unit number and position in the same refrigerant line can be confirmed. A header unit is selected, the indoor unit
numbers in the same refrigerant system are successively displayed, and then its indoor unit fan is turned on.
1
TEST
Push the timer time
+
buttons simultaneously for 4 seconds or more.
Firstly, the line 1, CODE No.
(Address Change) is displayed. (Select outdoor unit.)
2
SWING/FIX
Using
and
buttons, select the line
address.
3
SET
Using
button, determine the selected line
address.
• The indoor address, which is connected to the
refrigerant system of the selected refrigerant system is
displayed and the fan is turned on.
4
Every pushing
button, the indoor unit
numbers in the same refrigerant system are
successively displayed.
• Only fan of the selected indoor unit operates.
To select another system address
5
CL
Push
button to return to procedure
• The indoor address of another line can be successively
confirmed.
6
TEST
Push
button to finish the procedure.
39-EN
CODE No.
SET DATA
SETTING
UNIT No.
R.C.
No.
TEMP.
ON / OFF
I T
M
E
R
S
E
T
FAN
M
O
D
E
3
TIME
SAVE
VENT
End
FILTER
RESET
TEST
SET
CL
SWING/FIX
UNIT LOUVER
1
Operation procedure
1
2
3
End
CODE No.
SET DATA
SETTING
UNIT No.
R.C.
No.
TEMP.
ON / OFF
I T
M
E
R
S
E
T
FAN
M
O
D
E
1
TIME
SAVE
VENT
FILTER
RESET
TEST
SET
CL
SWING/FIX
UNIT LOUVER
6
3
2
.
Operation procedure
1
2
3
4
5
6
End
Change of indoor address from wired remote controller
▼ To change the indoor address in individual operation (Wired remote controller : Indoor unit = 1 : 1)
or group control (When the setup operation with automatic address has finished, this change is available.)
[Procedure] (Operation while the air conditioner stops)
1
Push simultaneously
(The firstly displayed unit No. indicates the header indoor unit in group control.)
2
In group control, select an indoor unit No. to be changed by
(The fan of the selected indoor unit is turned on.)
3
Using the setup temp.
4
1
Using the timer time
to change.
5
SET
Push
button.
2
6
Using the
button, select the unit No. to be changed at the next time.
Repeat the procedure
7
After the above change, push
8
If it is acceptable, push
3
5
8
2
1
4
5
– 20 –
SET
CL
TEST
+
+
buttons for 4 seconds or more.
/
buttons, set
to the CODE No.
/
buttons, change the displayed setup data to a data which you want
4
6
to
and change the indoor address so that it is not duplicated.
button to confirm the changed contents.
TEST
TEST button to finish confirmation.
CODE No.
SET DATA
SETTING
UNIT No.
R.C
No.
TEMP.
ON / OFF
TIMER SET
FAN
MODE
4
TIME
SAVE
VENT
FILTER
RESET TEST
SET
CL
SWING/FIX
UNIT LOUVER
2, 6, 7
Operation procedure
1
2
3
4
5
6
7
8
End
button.
EN
40-EN