REQUIREMENT
• When a group control is performed over multiple
refrigerant systems, be sure to turn on the power
supplies to all of the indoor units connected, so that
the address set-up can be completed correctly.
• If turning on the power for each refrigerant system to
set up the addresses, a header indoor unit must be set
for each system. Therefore, an alarm code "L03"
(Duplicated header indoor units) will be displayed
during in operation after the address setup has been
completed. In this case, change the group address
using the wired remote controller so that only one
header indoor unit is set-up.

◆ Address setup procedure 2

1
Using SW13 and 14 on the interface P.C.
board on the outdoor unit in each system,
set up the system address for each system.
(At shipment the address is set to 1 from the factory)
NOTE
Be careful not to duplicate with any other refrigerant systems
or other line (system) addresses.
Line (System) address switch on outdoor interface P.C. board
SW13
SW14
Line
address
1
2
3
4
1
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
: Is not used for setup of line address. (Do not change setup.)
2
Check that the relay connectors between [U1U2] and [U3U4] terminals are come out in all outdoor
units to which the central control is connected. (Factory default : No connection of connector)
3
Turn on power of indoor / outdoor. (In order of indoor → outdoor)
4
After approx. 1 minute, check that 7-segment display is
on the interface P.C. board.
U. 1. L08 (U. 1. flash)
5
Push SW15 and start setup the automatic address.
(Max. 10 minutes for 1 line (Usually, approx. 5 minutes))
6
Auto 1 → Auto 2 → Auto 3
When the count
in 7-segment display section, and it changes from
U. 1. - - - (U. 1. flash)
to
U. 1. - - - (U. 1. light)
setup finished.
7
4
6
Procedure
to
are repeated in other refrigerant systems.
35-EN
Group control over
(Example)
multiple refrigerant system
Wire
systematic
Outdoor
Outdoor
diagram
Indoor
Indoor
Indoor
Remote
controller
Interface P.C. board
ON
ON
ON
1
2 3 4
1
2 3 4
1
2 3 4
SW11
SW12
SW13
ON
ON
ON
ON
1
2 3 4
1
2 3 4
1
1
SW06
SW07
SW08
SW09
: Switch ON, ✕ : Switch OFF)
(
SW13
Line
address
3
4
1
2
3
4
1
15
16
17
18
19
20
21
22
23
24
25
26
27
28
is displayed
2
, the
Relay connector
U1
U2
For control
wiring between
indoor and
outdoor
8
When address setup has finished in all the
systems, turn off SW30-2 on the interface P.C.
boards of the lines connected to the identical central
control except a line with least line address number.
(Terminator resistors of the wires in the central
control line of indoor / outdoor are unified.)
9
Connect the relay connector between [U1U2] and
Indoor
[U3U4] terminals of the outdoor unit for each
refrigerant line.
10
Then set up the central control address.
(For the central control address setup, refer to the
Installation manual of the central control devices.)
ON
1
2 3 4
Switch setup
SW14
ON
(Example in case of central control over refrigerant system)
2 3 4
1 2 3 4
Outdoor side (Manual setup)
SW10
* Manual setup is necessary for column of which letter color is reversed.
Outdoor interface
P.C. board
SW13, 14
(Line address)
SW14
SW30-2
2
3
4
Terminator resistor of
indoor / outdoor communi-
cation line / central control
communication line
Relay connector
remote controller
Indoor units
(automatic setting)
Line address
Indoor unit address
Group address
CAUTION
For relay connector
U3
U4
Never connect a relay connector until address setup for all the refrigerant systems finishes;
For wiring of
central control
otherwise address cannot be correctly set up.
system
– 18 –
ON
1
2 3 4
SW11
ON
1
2 3 4
SW06
Outdoor unit
Outdoor unit
1
2
OFF after
ON
address setup
Short after
Short after
address setup
address setup
Outdoor unit
Outdoor unit
U3 U4
U3 U4
U3 U4
Central
U1 U2
U1 U2
Relay
Relay
connector
connector
U1 U2
U1 U2
U1 U2
A B
A B
A B
Remote
Remote
Remote
controller
controller
controller
Individual
Group
1
1
2
1
2
1
0
0
1
Interface P.C. board
ON
1
2
SW30
SW30
ON
ON
ON
1
2 3 4
1
2 3 4
1
2 3 4
SW12
SW13
SW14
ON
ON
ON
ON
1
2 3 4
1
1
2 3 4
1 2 3 4
SW07
SW08
SW09
SW10
SW15
SW04
SW05 SW15
7-segment
display
D600 D601 D602 D603 D604
SW01
SW02 SW03
1
1
1
Setup factory
Outdoor unit
default
3
1
OFF after
ON
address setup
Short after
Open
address setup
Outdoor unit
U3 U4
U1 U2
Relay
connector
U1 U2
U1 U2
A B
A B
Remote
controller
2
3
2
1
2
0
EN
36-EN