cLeARANceS

cLeARANceS to coMBuStIBLeS
Follow these instructions carefully to ensure safe installation. Failure to
follow instructions exactly can create a fire hazard.
the appliance cannot be installed on a carpet, tile or other combustible
material other than wood flooring. If installed on carpet or vinyl flooring, the
appliance shall be installed on a metal, wood or noncombustible material
panel extending full width and depth of the appliance.
Side Wall
Ceiling
Noncombus-
tible Facing
9" (229 mm)
Minimum
Figure 5 -
Clearances to Combustible
Materials
FP2711
combustible clearances
51D0528
Combustible
Mantel
12" (305 mm)
Max. Depth
44 "
(1137 mm)
6" 
(152 mm)
12" (305 mm)
Minimum
MANteL cLeARANceS
Note: the combustible area above the facing must
not protrude more than 3/4" from the facing. If it does,
it is considered a mantel and must meet the mantel
requirements listed in this manual.
heARth RequIReMeNtS
The fireplace must be installed on a non-combustible hearth
extending a minimum of 12" from the fireplace opening
(local codes may require a larger hearth). The hearth must
also extend to both sides of the face (see the table above
for the exact width of the face).
46 "
(1187 mm)
FP2711
LX Series Direct Vent Gas Fireplace
9