Horizontal (Through The Wall) Termination; Configuration - MHSC LEXINGTON LX32DV Installation And Operating Instructions Manual

Direct vent gas fireplace
Table of Contents

Advertisement

LX Series Direct Vent Gas Fireplace
FP2715
Apply Mastic to
All Four Sides
Figure 17 -
Installing Horizontal Vent Cap
For vinyl siding, stucco, or wood exterior use vinyl siding
FP2715
standoffs between vent cap and exterior wall. The vinyl
horiz cap w shield
siding standoff prevents excessive heat from melting the
vinyl siding material. Bolt the vent cap to the standoff. Apply
non-hardening mastic around outside edge of the standoff
instead of the vent cap assembly. Use wood screws pro-
vided to attach the standoff. Figure 18
FP2716
Apply Mastic to
All Four Sides
Wood Screw
Figure 18 -
Install Vinyl Siding Standoff
5. Slide fire stop over the vent pipe before connecting the
Fp2716
horizontal run to the vent cap. Figure 19
vinyl siding standoff
6. The pipe overlap should be a minimum of 1Z\v". Apply
silicone to the outer pipe connection. Fasten all vent
connections with screws provided.
7. Slide fire stop against the interior wall surface and attach
with screws. Figure 19
18
Deflecting Shield
Vent Cap
T
H O
Wood Screw
Cut Vinyl Siding Away
to Fit Standoff
Deflecting Shield
Standoff
T
H O
Screw
Vent Cap
(Horizontal
Termination)
FP1957
Figure 19 -
Connect Vent Cap with Horizontal Vent Pipe
hoRIZoNtAL (thRouGh the WALL) teR-
MINAtIoN coNFIGuRAtIoNS
Since it is very important that the venting system main-
tain its balance between the combustion air intake and
the flue gas exhaust, certain limitations as to vent con-
figurations apply and must be strictly adhered to.
The Vent Graph, showing the relationship between vertical
and horizontal side wall venting, will help to determine the
various dimensions allowable. Refer to Page 16
Minimum clearance between vent pipes and combus-
tible materials is 3" on top and 1" from bottom and
sides unless otherwise noted.
When vent termination exits through foundations less than
20" below siding outcrop, the vent pipe must flush up with
the siding.
It is best to locate the fireplace in such a way that minimizes
the number of offsets and horizontal vent length.
Vent
Cap
When installing the appliance as a rear
vent unit, the 90°, 45° transition elbow
attached directly to the rear of the unit is
Not INcLuDeD in the following criteria
and calculations, and unless specifically
mentioned should be ignored when
calculating venting layouts.
The horizontal vent run refers to the total length of vent
pipe from the flue collar of the fireplace (or the top of the
Transition Elbow) to the face of the outer wall.
The maximum number of 90° elbows per side wall
installation is three (3). Figure 20
If a 90° elbow is fitted directly on top of the fireplace
flange the maximum horizontal vent run before the ter-
mination or a vertical rise is 36" (914 mm). Figure 21
If a 90° elbow is used in the horizontal vent run (level
height maintained) the horizontal vent length is reduced
by 36" (914 mm). This does not apply if the 90° elbows
are used to increase or redirect a vertical rise. Figure
23
VeNtING INStALLAtIoN
Interior Wall
Surface
Screw
FP1957
install firestop
Fire Stop
Assembly
Horizontal
Vent Pipe
51D0528