Vitodens Rigid and Flex Venting Systems Installation
When terminating the vertical vent pipes of multiple
Vitodens boilers, a minimum clearance of 4 inches
(100 mm) is required between the outside edges of
each vent pipe.
When terminating the horizontal vent pipes of multiple
Vitodens boilers, a minimum clearance of 12 inches
305 mm) is required between the outside edges of each
vent pipe.
Note: termination elbows can be 45
o
o
or 90
.