Rigid Venting Systems Installation Instructions

Component Installation Guide

Coaxial vent termination installation

1
3
Fig. 7 Coaxial vent termination
Legend
1 Vent termination
2 Wall flashing (inside)
3 Wall flashing (outside)
Fig. 8
2
6 in. (152 mm)
Offset
Side Wall Vent Installation (Coaxial)
Table 4. Wall opening information
Vent system
60/100
80/125
100/150
110/160

Side wall vent termination installation

1. Provide side wall opening (see table above) to install
vent termination.
2. Slide vent termination 1 with wall flashing 3 into
opening (drain openings 5 must be located on the
outside of the wall, pointing downward).
3. Attach wall flashing 2 to inside of wall using the
screws and plugs provided.
4. Attach wall flashing 3 to outside of wall.
IMPORTANT
If required the vent termination may be shortened.
IMPORTANT
Potential gaps between the vent-air intake and the
surrounding construction which may cause air, rain or flue
gases to leak into the wall or the building, must be sealed
with approved outdoor sealant/caulking to prevent leakage
of any kind.
When installing a side wall vent system with the minimum
equivalent vent length (87º elbow and vent termination, a
wall thickness of at least 6 in. (152 mm) is required.
For walls with a thickness less than 6 in. (152 mm),
means must be provided to offset the boiler from the wall
(see fig. 8).
Opening Ø
4a in. (108 mm)
5a in. (133 mm)
6e in. (160 mm)
11
6
/
in (170 mm)
16
17