Horizontal Pipe System - Viessmann Vitodens 200-W WB2B Series Installation Instructions Manual

Rigid and flex pipe venting systems
Hide thumbs Also See for Vitodens 200-W WB2B Series:
Table of Contents

Advertisement

Direct Venting (Two-pipe System)
Component Parts of the PP(s) Venting System

Horizontal pipe system

B2HA 45, 60,
88,100,
112, 150
B2HB 45, 57
B2HA 19, 28, 35
B2HB 19, 26, 35
B2TA 19, 35
B2TB 19, 35
WB1B 26, 35
WB2B 19, 26, 35
B2HA 19, 28, 35
B2HB 19, 26, 35
B2TA 19, 35
B2TB 19, 35
IMPORTANT
For PP(s) systems, all exhaust vent and air intake piping
and elbows exposed outside, must be UV resistant
polypropylene (supplied by the vent manufacturer).
Always include vent termination length in calculations.
52
Vitodens Rigid and Flex Venting Systems Installation
(continued)
Legend
A Combustion air intake
B Flue gas outlet
1 Boiler vent pipe adaptor
2 Double pipe adaptor
3 Air intake adaptor (PVC, CPVC, ABS)
4 PP(s) adaptor (WB2B 80, 105 and
B2HA 80, 88, 100, 112, 150 only with M&G system)
5 90º elbows
6 Combustion air intake straight pipe
7 Straight vent pipe
8 Pipe support
9 Wall plate
qP Bird screen
Legend
A Boiler vertical coaxial termination
B Air intake adaptor (if required) field supplied
C Pipe support system
D Vent adaptor (if required) field supplied.
E Long vent length 3.3 ft. (1 m)
F 90º elbows
G Short vent length 1.6 ft. (0.5 m)
H 2 pipe to coaxial adaptor (field supplied). Consult
Venting Manual.
I Horizontal coaxial termination
J Bird screen