Discharge Pipework - Potterton Promax Store 24 Installation And Service Manual

Condensing boiler with integrated hot water storage
Hide thumbs Also See for Promax Store 24:
Table of Contents

Advertisement

If the initial cold fill pressure is 1.0 bar:
expansion vessel size = 0.11 x system volume
This fill pressure will allow the maximum expansion
capacity, though any minor loss of water will result in
a rapid pressure drop. An additional expansion
vessel is only required if the total system volume
exceeds 98 litres.
This includes the 4 litre primary circuit volume
within the Promax Store boiler - thus radiator and
pipework volume should not exceed 94 litres.
Pipework above boiler
Air vents must be fitted at the highest positions on flow
and return pipes and at any point where air is likely to
collect.
TRV s in System
An automatic bypass valve is built into the boiler to
allow thermostatic radiator valves to be fitted. This can
be switched into or out of circuit as required.

1.7 Discharge Pipework

It is a requirement of Building Regulation G3 that any
discharge from an unvented system is conveyed to
where it is visible, but will not cause danger to persons
in or about the building. The tundish and discharge
pipes should be fitted in accordance with the
requirements and guidance notes of Building
Regulation G3. The G3 Requirements and Guidance
section 3.9 are reproduced in the following sections.
Information Sheet No. 33 available from the British
Board of Agrement gives further advice on discharge
pipe installation. For discharge pipe arrangements not
covered by G3 Guidance or BBA Info Sheet No.33
advice should be sought from either your local Building
Control Officer or Potterton.
G3 Requirement "...there shall be precautions ... to
ensure that the hot water discharged from safety
devices is safely conveyed to where it is visible but will
not cause danger to persons in or about the building."
G3 Guidance SECTION 3.9
The discharge pipe (D1) from the vessel up to and
including the tundish is generally supplied by the
manufacturer of the hot water storage system. Where
otherwise, the installation should include the discharge
pipe(s) (D1) from the safety device(s). In either case
the tundish should be vertical, located in the same
space as the unvented hot water storage system and
be fitted as close as possible and within 600 mm of the
safety device e.g. the temperature relief valve. Note:
The tundish is factory fitted during manufacture of
the Promax Store. The discharge pipe (D2) from the
tundish should terminate in a safe place where there is
no risk to persons in the vicinity of the discharge,
preferably be of metal and:
18
a.be at least one pipe size larger than the nominal
outlet size of the safety device unless its total
equivalent hydraulic resistance exceeds that of a
straight pipe 9m long i.e. discharge pipes between
9m and 18m equivalent resistance length should
be at least two sizes larger than the nominal
Outlet size of the safety device, between 18 and
27m at least 3 sizes larger, and so on. Bends must
be taken into account in calculating the flow
resistance. Refer to Fig. 8, Table 1 and the worked
example.
An alternative approach for sizing discharge pipes
would be to follow BS 6700:1987 Specification for
design installation, testing and maintenance of
services supplying water for domestic use within
buildings and their curtilages. Appendix E. section E2
and table 21.
b.have a vertical section of pipe at least 300 mm long,
below the tundish before any elbows or bends in the
pipework.
c. be installed with a continuous fall.
d.have discharges visible at both the tundish and the
final point of discharge, but where this is not
possible or practical, there should be clear visibility
at one or other of these locations. Examples of
acceptable discharge arrangements are:
i. ideally below a fixed grating and above the
water seal in a trapped gully.
ii. downward discharges at low level; i.e. up to
100mm above external surfaces such as car
parks, hard standings, grassed areas etc. are
acceptable providing that where children may
play or otherwise come into contact with
discharges a wire cage or similar guard is
positioned to prevent contact, whilst maintaining
visibility.
iii. discharges at high level; e.g. into a metal hopper
and metal down pipe with the end of the
discharge pipe clearly visible (tundish visible or
not) or onto a roof capable of withstanding high
temperature discharges of water and 3m from
any plastic guttering system that would collect
such discharges (tundish visible).
iv. where a single pipe serves a number of
discharges, such as in blocks of flats, the
number served should be limited to not more
than 6 systems so that any installation
discharging can be traced reasonably easily.
The single common discharge pipe should be at
least one pipe size larger than the largest
individual discharge pipe (D2) to be connected.
If unvented hot water storage systems are
installed where discharges from safety devices
© Baxi Heating UK Ltd 2015

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents