CDVX Series Direct Vent Gas Fireplace
36CDVXT Vertical Venting
How to Use the Vent Graph
The vent chart should be read in conjunction with the
following vent installation instructions to determine the
relationship of the vertical and horizontal dimensions of
the vent system.
1. Determine the height of the center of the horizontal
vent pipe exiting through the outer wall. Using this
dimension on the Sidewall Vent Graph (Fig. 42),
locate the point intersecting with the slanted graph
line.
2. From the point of this intersection, draw a vertical
line to the bottom of the graph.
3. Select the indicated dimension, and position the
fireplace in accordance with same.
Example A:
If the vertical dimension from the floor of the fireplace
is 11' (3.4 m) the horizontal run to the face of the outer
wall must not exceed 14' (4.3 m).
Example B:
If the vertical dimension from the floor of the unit is 7'
(2.14 m), the horizontal run to the face of the outer wall
must not exceed 8¹⁄₂' (2.6 m).
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
3
4 5 6
7 8
9 10 11 12 13 14 15 16 17 18 19 20
Horizontal dimension from the outside face of the
wall to the center of the fireplace vent flange
Sidewall vent graph showing the relationship between vertical
CFM102
and horizontal dimensions for a Direct Vent flue system.
DV Graphic
Fig. 42 Sidewall venting graph. (Dimensions in feet)
9/28/00 sta
22
eg: A
eg: B
36 CDVXT Top Vent Baffle
The 36CDVXT is shipped with a restrictor installed in
the unit. This allows for a better flame when installing a
vertical venting configuration. Below is a rough esti-
mate of opening positions based on vent length. This
is a guide. More fine tuning can be done by a qualified
installer. Adjust the restrictor so there is no lifting of the
flame from the burner tube and the flame is not dirty to
create soot.
To adjust:
1. Loosen the two (2) screws securing the flue baffle.
(Fig. 43)
2. Remove two (2) screws from either side of the flue
box. (Fig. 43) Adjust the restrictor. (Fig. 44)
3. Tighten the screws in the flue baffle and insert the
two (2) screws removed earlier through the slots in
the restrictor.
Flue Box
Loosen
Screws
Fig. 43 Loosen screws securing flue baffle.
Restrictor
Up to 10' (3 m) X = 1¹⁄₂" (38 mm)
10' to 40' (12 m) X = 1¹⁄v" (32 mm)
Fig. 44 Adjust the restrictor for best flame appearance.
Flue Pipe
Remove Screws
from Either side
Flue Baffle
X
FP1799
CDVXT restrictor
4/07
20012253
FP1797
FP1799