VENTING LAYOUT

Selection of components and details of venting layout should adhere to
the following guidelines:
Vent terminations must not be recessed in walls or siding.
All through-the–wall terminations within 58" Horizontal distance of the
fireplace must have a Montigo Heat Shield (RHS102) installed. See
Section 3-3-3.
All through-the-wall terminations beyond 58" Horizontal distance of the
fireplace must have a Montigo Heat Shield (RHS101) installed. See
Section 3-3-3.
Once the proposed venting layout has been determined refer to either
Figure 15 or Figure 16 to ensure the layout is acceptable.
Wall mounted Terminations
The following details are some possible configurations for Wall
mounted terminations. See below.

Wall Mounted Terminations: Top Vent

All dimension lengths for vertical or horizontal runs are measured from
center of the vent pipe.
Venting runs must fall within the limits set by the venting graphs, see Figure 15.
The Venting Graph
Measure the vertical height from the fireplace hearth to the centre of the termination
and the horizontal run from the fireplace flue collar to the wall flange of the termination.
Plot on the Venting Graph Figure 15 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the installation is
acceptable.
Example a: (acceptable Installation)
If the vertical dimension from the hearth is 90" and the horizontal
run to the wall flange of the vent termination is 60", this would be
an acceptable installation.
Example B: (acceptable Installation)
If the vertical dimension from the hearth is 60" and the horizontal
run to the wall flange of the vent termination is 36", this would be
an acceptable installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the floor of the fireplace is 60" and
the horizontal run to the wall flange of the vent termination is 144",
this would nOT be an acceptable installation.
XG0213 - 020111
Installation
Acceptable vent run
within non-shaded area.
Figure 15. Top Vent Venting Graph for wall mounted terminations.
Flex section
Hearth
Figure 15a. Top Vented, wall mounted installation with1 elbow (1 one 90°
bend). The vent run must comply with Venting Graph for Top vent, wall
mounted terminations, Figure 15.
Figure 15b. Top Vented, wall mounted Multi-elbow installation. See Venting
Graph for Top vent, wall mounted terminations, Figure 15.
H(L)38DF-CLCR Corner Gas Fireplace
A
C
B
46" Rigid
50" Flex
If your installation does not fall
18"
within the venting graph para-
Unacceptable vent run
meters, please contact Montigo
for Power Venting options.
within shaded area.
18" Max
RHS102 Heat
Shield
Termination
Wall
30"min
Solid
Section
Flex
Section
Hearth
46" Min. Rigid Pipe
50" Min. Flex Pipe
RHS101 Heat
Shield
Termination
Exterior
Wall
Page 11