1.0 IMPORTANT INSTALLATION POINTS

1.1 The Multipoint unvented water heater is factory fitted with two
Temperature/Pressure Relief Valves which must not be removed, blocked
or restricted in any way.
1.2 Expansion MUST be accommodated within the system. The Multipoint
75/100 incorporates an expansion vessel and check valve for this
purpose.
1.3 The Multipoint water heater must be installed by a competent installer in
accordance with Building Regulation G3 (England and Wales), Technical
Standard P3 (Scotland) or Building Regulation P5 (Northern Ireland).
FAILURE TO PROVIDE ADEQUATE TEMPERATURE AND PRESSURE
RELIEF WILL INVALIDATE ANY GUARANTEE AND LEAD TO A
DANGEROUS INSTALLATION.
WARNING: IF WATER FLOWS FREELY FROM THE PRESSURE
RELIEF VALVE OR THE TEMPERATURE/PRESSURE RELIEF
VALVES, THE ELECTRICITY SUPPLY MUST BE SWITCHED OFF
IMMEDIATELY. CONTACT THE HEATRAE SADIA SERVICE TEAM
(TEL: 01603 420330) OR AN APPROVED INSTALLER.

2.0 GENERAL REQUIREMENTS:

2.1 The Multipoint must be vertically wall mounted using the wall bracket
supplied. The water connections must always be at the bottom of the
unit.
2.2 Enough space should be left below the unit for pipe connections and
above the unit for access to the Temperature/Pressure Relief Valves (400
mm minimum). Refer to Figure 1 and the Dimensions Table to determine
a suitable position for the heater.
2.3 Ensure that the wall can support the full weight of the unit and that there
are no hidden services (electricity, gas or water) below the surface of the
wall.
2.4 DO NOT install where the unit may freeze.
2.5 National Wiring Rules may contain restrictions concerning the installation
of these units in bathrooms.