Appendix 3: Parameter list level 1 (Pr1)
Parameter
Description
C01
Compressor cut-in pressure setpoint
C02
Compressor cut-out pressure setpoint
C07
Refrigerant selection for regulation
C16
Digital compressor setpoint
C17
Proportional band for compressor regulation
C21
Cycle time for digital compressor
C24
Minimum capacity for digital compressor
C25
Maximum capacity for digital compressor
E39
Condenser setpoint
E46
Regulation band of variable fan
N01
Current minute
N02
Current hour
N03
Date of month
N04
Month
N05
Year
T18
Access to Pr2 level
Table 24: Parameters level 1
C6.1.6/0513-0515/E
Factory
Unit
setting
[bar]
4.0
Not used for Digital CFDE
[bar]
2.0
Not used for Digital CFDE
R22, R407A, R407F, R507,
[-]
R404A
N40,DR33, R134a, R407C
[bar]
3.3
Not used for CFME & CFLE
[bar]
2.0
Not used for CFME & CFLE
[Sec]
10
Not used for CFME & CFLE
[%]
20
Not used for CFME & CFLE
[%]
100
Not used for CFME & CFLE
[°C]
35.0
[°C]
10.0
[-]
[-]
[-]
[-]
[-]
[-]
[-]
[-]
[-]
[-]
[-]
[-]
Password: 3 2 1