to carry out a visual inspection of the low voltage crimped terminals at least once every
6 months.
5.4
Routine leak testing
All joints within the system should be leak-tested as part of a regular maintenance schedule.
5.5
Condenser fan(s) & motor(s)
A yearly inspection of these items is recommended. Fastenings can come loose, bearings may
wear and fans may require cleaning of solid deposits that can cause rotational imbalance.
Motors come with lifelong lubrication bearings that do not require lubricating on a routine basis,
but just need to be checked for wear.
6
Certification & approval
The piping is in compliance with the Pressure Equipment Directive PED 97/23/EC (Art.3 §3 -
Sound Engineering Practice).
The components of the condensing units carry a CE mark as far as required and thereby
establish conformity with the relevant directives.
Conformity Declarations for components are available as far as required.
The units are in conformity with the low voltage directive. The applied harmonised standard
is EN 60335-2-891 (Safety Household and Similar Electrical Appliance, Part 2: Particular
requirements for commercial refrigerating appliances with an incorporated or remote
refrigerant condensing unit or compressor).
To incorporate these products into a machine the Manufacturer's Declaration of
Incorporation has to be respected.
7
Dismantling & disposal
Removing oil and refrigerant:
1.
Do not disperse in the environment.
2.
Use the correct equipment and method of removal.
3.
Dispose of oil and refrigerant properly.
4.
Dispose of unit properly.
DISCLAIMER
1. The contents of this publication are presented for informational purposes only and are not to
be construed as warranties or guarantees, express or implied, regarding the products or
services described herein or their use or applicability.
2. Emerson Climate Technologies GmbH and/or its affiliates (collectively "Emerson"), as
applicable, reserve the right to modify the design or specifications of such products at any
time without notice.
3. Emerson does not assume responsibility for the selection, use or maintenance of any
product.
Responsibility for proper selection, use and maintenance of any Emerson product
remains solely with the purchaser or end user.
4. Emerson does not assume responsibility for possible typographic errors contained in this
publication.
30
C6.1.6/0513-0515/E

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for FISCHER [CF] EASY

Table of Contents