FISCHER [CF] EASY User Manual page 62

Outdoor condensing units
Table of Contents

Advertisement

Available languages

Available languages

Electronic controller XCM25D – Features
2.8
The XCM25D controller is designed to be a powerful, flexible controller for use in multiple
applications. It has been developed for condensing units and allows the adjustment of all
relevant parameters by the user.
2.8.1 Description
WARNING
Electrical shock hazard! Serious personal injuries! There are unused
fast-on pins (C1 & D02) on the XCM25D which could be under voltage. They
are covered by insulated fast-on flags in the factory. Handle carefully when
removing insulating flags during service on site.
The controller is designed for usage in an outdoor refrigeration unit. It is rated to be used for the
following environment:
Outdoor controller ambient temperature for operation: -40C to 60C
Ambient temperature for storage: -40C to 80C
Maximum humidity: 90% at 48C (non-condensing)
Board power: 24V AC +15%/-20%
Voltage sensing capabilities - Single phase: 100-120, 200-240V AC ± 10%
Voltage sensing capabilities - Three phase: 200-240, 380-460, 575V AC ± 10%
The units of measure are selectable. The factory default unit is [bar] (always considered relative)
for pressure and [°C] for temperature.
Figure 6: Electronic controller
2.8.2 Functionality
The controller allows easy commissioning by the technician with the factory settings at the
highest program level. It also offers the possibility to make substantial changes to the system
optimization in further programming levels. Advanced functionality can also be activated.
The following functions are covered by the controller:
Condensing unit control
Case control
Condenser fan control
Defrost
Voltage and current sensing (compressor protection)
Liquid and vapour injection
System EXV control
Digital compressor control
NOTE: The XCM25D controller on the [ CF ] EASY units includes all the functions
necessary for unit control. For additional functionalities please contact your local
Application Engineering representative.