LABEL
DESCRIPTION
5.7.1 Liquid Injection Control
F01
Liquid injection setpoint
F02
Max DLT temperature before full open injection
F03
Min DLT temperature before close injection
5.7.4 Injection Error Handling - DLT failure
F04
Mid-coil limp along for DLT failure - Mid-coil 1
F05
Mid-coil limp along for DLT failure - Mid-coil 2
F06
Mid-coil limp along for DLT failure - Mid-coil 3
F07
Mid-coil limp along for DLT failure - Mid-coil 4
F08
Mid-coil limp along for DLT failure - Mid-coil 5
F09
Mid-coil limp along for DLT failure - Valve opening 1
F10
Mid-coil limp along for DLT failure - Valve opening 2
F11
Mid-coil limp along for DLT failure - Valve opening 3
F12
Mid-coil limp along for DLT failure - Valve opening 4
F13
Mid-coil limp along for DLT failure - Valve opening 5
5.7.4 Injection Error Handling - DLT failure and Mid-Coil failure
F14
Ambient limp along for DLT and mid-coil failure - Temperature 1
F15
Ambient limp along for DLT and mid-coil failure - Temperature 2
F16
Ambient limp along for DLT and mid-coil failure - Valve opening 1
F17
Ambient limp along for DLT and mid-coil failure - Valve opening 2
5.7.6 Injection Initial Opening Settings
EVI EXV Initial opening – Ambient 1
F18
EVI EXV Initial opening – Ambient 2
F19
EVI EXV Initial opening – Ambient 3
F20
EVI EXV Initial opening – Ambient 4
F21
EVI EXV Initial opening – Valve opening 1
F22
EVI EXV Initial opening – Valve opening 2
F23
EVI EXV Initial opening – Valve opening 3
F24
EVI EXV Initial opening – Valve opening 4
F25
EVI EXV Initial opening – Valve opening 5
F26
5.7.6 Injection Initial Opening Settings - if Ambient and Mid-Coil sensor failure
F27
EVI EXV Initial opening with sensor failure
5.7.7 Vapour Injection Mode
F28
Differential between the vapour inlet and the vapour outlet temperature for R404A
F29
Differential between the vapour inlet and the vapour outlet temperature for R507
F31
Differential between the vapour inlet and the vapour outlet temperature for R22
F32
Differential between the vapour inlet and the vapour outlet temperature for R407C
C6.1.6/0513-0515/G
F33
Differential between the vapour inlet and the vapour outlet temperature for R407A
ZXME
Level
°C
110.0
L2
°C
118.0
L2
°C
80.0
L2
°C
60.0
L2
°C
50.0
L2
°C
40.0
L2
°C
30.0
L2
°C
20.0
L2
%
100
L2
%
80
L2
%
60
L2
%
35
L2
%
15
L2
°C
30.0
L2
°C
20.0
L2
%
80
L2
%
35
L2
°C
°C
°C
°C
%
%
%
%
%
%
°C
°C
°C
°C
°C
ZXLE
Level
ZXDE
110.0
L2
118.0
L2
80.0
L2
35.0
L2
30.0
L2
25.0
L2
15.0
L2
60
L2
40
L2
30
L2
20
L2
10
L2
40
L2
5.0
L2
5.0
L2
5.0
L2
10.0
L2
10.0
L2
Level
39

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for FISCHER [CF] EASY

Table of Contents