5: Installation - Indirect Units

5.1 Boiler Selection
The Megalife indirect models are suitable for use with most gas, oil or electric boilers. The boiler used can either be
a sealed system or open vented type. The maximum primary circuit pressure is 3.5 bar. If an open vented type boiler
is used it must be fed from a separate boiler feed and expansion cistern, it MUST NOT be fed from the Megalife
cold water feed cistern.
The primary flow from the boiler MUST be pumped. Gravity circulation will not work due to the special design of
the primary heat exchanger. It is recommended that an air bleed point or automatic air vent is incorporated in the
primary return pipework close to the Megalife unit to aid in bleeding air from the primary heating coil.
The boiler should be fitted with adequate thermal control. This will normally include a primary flow thermostat and a
safety over temperature cut-out. The boiler flow temperature should usually be set to 82
to primary heat exchanger 90
The boiler cannot be vented through the Megalife unit.
5.2 Indirect Thermal Controls
Control of the storage temperature when indirectly heated is provided by the fitted cylinder thermostat. The control is
located under the white plastic cover located to the right of the indirect coil connections. If necessary the temperature
can be adjusted by inserting a flat bladed screwdriver in the adjustment knob and rotating. The minimum thermostat
setting is 10°C. Adjustment represents a temperature range of 10°C to 72°C (See Fig. 04, page 9). If in any doubt
contact a competent electrician.
5.3 Wiring
All electrical wiring should be carried out by a competent electrician and be in accordance with the latest I.E.E.
Wiring Regulations.
The Megalife indirect thermostat and thermal cut-out are factory pre-wired. It is recommended that these controls are
wired in series with a suitable 2 or 3 port motorised valve to control the primary flow through the heater coil. Wiring
to external controls is made via the terminal block fitted. The cable should be routed through the aperture in the
terminal cover and secured using the cable grip provided. The indirect thermal cut-out MUST NOT be bypassed.
5.4 Heating System Controls
The controls provided with the Megalife will ensure the safe operation of the Megalife when heated by a primary
heat source. Other controls will be necessary to control the space heating requirements and times that the system is
required to function. Depending on the boiler selected, heating circuit design and controls used it may be beneficial
to incorporate a system bypass in the auxillary heating system pipework.
The Megalife is compatible with most heating controls, examples of electrical circuits are given in Fig's 05 and 06,
page 10. However, other systems may be suitable, refer to the controls manufacturers' instructions, supplied with
the controls selected, for alternative system wiring schemes.
5.5 Immersion Heater
The Megalife indirect units are supplied with an immersion heater which can be used as an alternative heat source
should the boiler supply need to be isolated from the Megalife unit. Refer to Sections 4.1 to 4.4 and Fig. 03, page 7
for details of the wiring and operation of the immersion heater.
8
C).
o
C (maximum flow temperature
o