Kitset Installation - Combustible Frame - Rinnai ROF4500 Operation & Installation Manual

Luminaire outdoor gas fire
Table of Contents

Advertisement

KITSET INSTALLATION - COMBUSTIBLE FRAME

Attach metal lintel and angled clearance brackets
Luminaire Outdoor Fire cabinet options are supplied with a metal lintel and angled clearance brackets.
These are required for installations where combustible framing is used.
• Metal lintels
• Angled clearance brackets
Metal lintel
Designed to sit about the unit and replace combustible framing in areas exposed to high
temperatures. The minimum distance above the unit to a combustible frame is 500 mm.
To fit
Step 1. Take out and undo four fastenening screws at
either end.
Step 2. Flip side sections 180° and loosely refit
screws.
Step 3. Adjust to desired length before tightening.
Angled clearance brackets
Designed to ensure combustible framing is greater than 25 mm from the sides of the unit as shown.
Top View - Open One-Sided Cabinet
timber stud
clearance bracket
Top View - Open See-Through Cabinet
timber stud
clearance
bracket
Rinnai Australia
Open One-Sided Cabinet (1), Open See-Through Cabinet (2)
Open One-sided Cabinet (4), Open See-Through Cabinet (4)
1225 mm (min)
cabinet
1180 mm (min)
1195 mm (max)
1225 mm (min)
cabinet
1180 mm (min)
1195 mm (max)
- 16 -
Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual
side sections need to be rotated 180°
and secured into framing above unit.
non combustible
cladding
non combustible cladding
min 500mm
470mm

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rof4501Rof4101Rof4102Rof4502Rof4100

Table of Contents