Luminaire® Outdoor Gas Fire Operation / Installation Manual Models: ROF4500, 4501, 4502, 4100, 4101, 4102 A luminous effect appliance. Not certified as a space heater. FOR OUTDOOR USE ONLY - this appliance shall not be installed or used indoors This appliance shall be installed in accordance with: •...
The A.G.A. Approval Number is shown on Data plate. Please keep this instruction booklet in a safe place for future reference. The Rinnai Luminaire® Outdoor Gas Fire does not need to be installed by a registered gas fitter if connecting to a 9 kg LPG cylinder.
MASONRY INSTALLATION ....................21 FREESTANDING UNIT ......................22 BURNER MATERIAL ......................22 CHECKLIST .......................... 23 INSTALLERS / GAS FITTER DETAILS ................23 CONTACT INFORMATION ....................23 Rinnai Australia - iii - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual...
Fascia Trim Kit Components x2 Instruction Manual/Warranty Sheet LP Hose & Regulator Assy x 1 Angle Brackets x 4 Lintel x 2 Stainless Steel Weather-Coverx1 Rinnai Australia - 1 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual...
Fascia Trim Kit Components x 1 M4 x 8 - 4 pieces M5 x 10 - 2 pieces Universal LPG - NG Gas Conversion Kit Rinnai Australia - 2 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual...
Personal injury or material damage may occur. Do not operate this appliance with the stainless steel weather cover on. Rinnai Australia - 3 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual...
Page 7
Before Installation Check that the Rinnai Luminaire Outdoor Gas Fire supplied is correct for the gas type being used. The gas type is clearly labelled on the appliance. Dataplate is located under left hand stone cover. Appliance is labelled “Universal LPG”, or “Natural Gas”. Label is located under right hand stone cover.
Page 8
Gas Cylinder 1. This Rinnai Luminaire Outdoor Gas Fire is designed for use with a 9 kg LP Gas cylinder. This cylinder should conform to AS 2030.1 - 1999. 2. The Rinnai Luminaire Outdoor Gas Fire is designed for use in the vapour withdrawal mode.
Page 9
If there is still a gas leak from the connection between the regulator and gas cylinder or any other connections contact your gas supplier or Rinnai for assistance. Connections other than the connection between the regulator and gas cylinder must only be altered by an authorised person.
At least 30% of the remaining wall area is open and unrestricted. In the case of balconies at least 20% of the total wall area shall be and remain open and unrestricted. Rinnai Australia - 7 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual...
CUSTOMER INFORMATION - OPERATION The Rinnai Luminaire Outdoor Gas Fire is easy to operate via the use of the control knob on the front of the Fire. All Rinnai appliances meet or exceed the safety Australian standards required for gas regulations.
ABNORMAL FLAME PATTERN Rinnai Luminaire Outdoor Gas Fire has a distinct flame pattern. This should look the same every time you start your Fire, after an initial warm up period of approximately 30 minutes. Abnormal flame performance and flame pattern can indicate a problem with your appliance, such as blocked gas injectors or burner material has shifted from when the unit was first installed.
SPECIFICATIONS Open Fronted Radiant / Convector Rinnai Luminaire Outdoor Gas Fire with manual control. Comes in 3 designs: • Freestanding table top unit • Open One sided cabinet (with optional glass bi-fold doors) • Open Two sided see-through unit (with optional glass bi-fold doors)
Closing the bi fold doors does not affect the operation of the appliance. Adequate ventilation is supplied via the louvres and gaps at the side and top of the unit. Rinnai Australia - 11 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual...
INSTALLATION APPLICATIONS The Rinnai Luminaire Outdoor Gas Fire is designed and required to be built into a permanent fixture. The table below details the available installations options, components needed and optional accessories. Installation Components Needed Optional Accessories Freestanding Unit •...
Ensure it is bent evenly and not kinked. See “Gas positioning diagram” on CAUTION page 21 for dimensions and positioning of the gas line opening. Rinnai Australia - 13 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual...
APPLIANCE LOCATION The Rinnai Luminaire Outdoor Gas Fire must be installed as a permanent fixture in an outdoor area. Determining and consideration of the position for the Rinnai Luminaire Gas Outdoor Fire will be dependent on the configuration of the unit purchased. Additional considerations such as protection...
KITSET INSTALLATION - NON COMBUSTIBLE FRAME Steel framing options are available for the one sided and two sided see-through units. For ease of installation Rinnai provide the durable steel frame as a kitset. Prepare framing dimensions Construct framing to specific installation dimensions shown.
1195 mm (max) Top View - Open See-Through Cabinet non combustible cladding timber stud 1225 mm (min) 470mm cabinet 1180 mm (min) clearance bracket 1195 mm (max) Rinnai Australia - 16 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual...
This offers wind protection when the unit is on and when not in use protection from wind, rain and nesting animals. The assembly fixed to the cabinet frame of the Rinnai Luminaire Outdoor Fire, so is only suitable for installations where a cabinet (also called a body assembly) has been installed....
DOOR ASSEMBLY Door Assembly Installation Instruction Kit contains: The Rinnai Luminaire Outdoor Gas Fire door assembly comes flat packed in 1 box and contains the following: Component Quantity Left hand glass panel and surround Right hand glass panel and surround...
Step 3. Remove the large 2 pcs M5 x 10 burner mounting screws on the left and right of the burner assembly anchoring the burner assembly to the cabinet. Step 4. Carefully remove the burner and set aside. Rinnai Australia - 19 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual...
Page 23
(1), then swing the assembly in at the bottom (2). The fascia assembly can then be secured into position using 2 pcs M4 x 8 screws (3). Rinnai Australia - 20 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual...
A suggested hole size is detailed below. Gas positioning diagram Install burner assembly Install burner assembly into non-combustible surround and fix in place with appropriate fasteners. Rinnai Australia - 21 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual...
This is common to all installations as below. BURNER MATERIAL Installation of the burner material is critical to correct operation of the Rinnai Luminaire Outdoor Gas Fire. Please note in each step the height at which the pumice, quartz stones or pebbles WARNING should sit.
____________________________________________________ ____________________________________________________ Phone: Mobile: )__________________ ____________________ Certificate of Compliance / Certification Number :__________________________ (* where applicable) Authorised Persons – License Number: _______________________________ Signed Date:___________________ :________________________ Rinnai Australia - 23 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual...
*Cost of a local call Higher from mobile or public phones. Head Office, New Zealand Internet: www.rinnai.co.nz E-mail: sales@rinnai.co.nz 105 Pavilion Drive 24 Hour Service Airport Oaks, Mangere, New Zealand Tel: 0800 746624 (0800 Rinnai) Tel: (09) 625 4285 Fax: (09) 624 3018 Rinnai Australia - 23 - ®...