Figure 7 - 120/240 VAC, 30 Amp Receptac/e
120V/240V
30A
2.4 HOW TO USETHEGENERATOR
See the "To Start the Engine"section for how to safely start and
stop the generator and how to connect and disconnect loads. If
there are any problems operating the generator, please call the
generatorhelplineat 1-888-436-3722.
,_
Never operate in an enclosed area or indoors!
NEVER use in the home, in a vehicle,
or in
partly enclosed
areas such as garages, EVEN
IF doors and windows are open! ONLY use
outdoors and far from open windows,
doors,
vents, and in an area that wiil not accumulate
deadly exhaust.
The engine exhaust fumes contain carbon
monoxide,
which you cannot see or smell.
This poisonous gas, if breathed
in sufficient
concentrations,
can cause unconsciousness
or
even death.
Adequate, unobstructed flow of cooling and
ventilating air is critical to correct generator
operation.
Do not alter the installation or permit
even partial blockage
of ventilation
provisions,
as this can seriously affect safe operation
of the generator. The generator MUST be
operated
outdoors.
This exhaust system must be properly
maintained.
Do nothing that might render the
exhaust
system unsafe or in noncompliance
with any local codes and/or standards.
Always
use a battery operated
carbon
monoxide
alarm indoors, installed according
to
the manufacturer's
instructions.
Using a generator
indoors CAN KiLL YOU IN MINUTES.
Generator
exhaust contains carbon monoxide.
This is
a poison you cannot see or smell.
NEVER use inside a home
or garage, EVEN iF doors
and windows are open.
Only use OUTSIDE and
far away from windows,
doors, and vents.
2.4.1 GROUND/NG THEGENERATOR W HENUSEDAS A
PORTABLE
This generator has an equipment ground that connects the
generatorframe components to the ground terminals on the AC
output receptacles (see NEC 250.34 (A) for explanation). This
allows the generatorto be used as a portable without grounding
the frame of the generatoras specifiedin NEC250.34.
SpecialRequirements
There may be Federalor State Occupational Safety and Health
Administration(OSHA)regulations,local codes, or ordinancesthat
apply to the intendeduse of the generator.
Please consult a qualified electrician, electrical inspector, or the
local agency havingjurisdiction:
* In some areas, generators are required to be registered with
local utility companies.
* If the generator is used at a construction site, there may be
additionalregulationswhich must be observed.
2.4.2 CONNECTING THEGENERATOR T OA BUILDING'S
ELECTR/CAL S YSTEM
Connections for standby power to a building's electrical system
must be made by a qualified electrician and in strict compliance
with all national and local electrical codes and laws. The
connection must isolatethe generatorpower from utility power or
other alternativepower sources.
NOTE:
Because the generator equipment ground is bonded to the AC
neutralwires in the generator, either a 3-poletransfer switch or
a 2 poletransfer switch with a switching neutral kit is required
to connectthis generator to a building load. In this application
thegeneratorbecomes a separately derived system (see NEC
250.20 (D)), and must be grounded in accordance with the
nationalor local electrical code requirements.