7-2. Operation Data

<Cooling>
Tempeature
Model name
condition(°C)
Indoor
Outdoor
80/67
98/75
(26.7/19.4) (35/23.9)
<Heating>
Tempeature
Model name
condition(°C)
Indoor
Outdoor
70/60
47/43
(21.1/15.6)
(8.3/6.1)
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition : 16 ft (5m)
Standard
RAS-
pressure
P Psia (MPa)
137 to 160
09EKV-UL
(0.9 to 1.1)
116 to 145
12EKV-UL
(0.8 to 1.0)
Standard
RAS-
pressure
P Psia (MPa)
363 to 392
09EKV-UL
(2.5 to 2.7)
377 to 406
12EKV-UL
(2.6 to 2.8)
Heat exchanger
pipe temp.
T1 °F (°C)
T2 °F (°C)
54 to 57
99 to 102
(12 to 14)
(37 to 39)
52 to 55
104 to 107
(11 to 13)
(42 to 44)
Heat exchanger
pipe temp.
T1 °F (°C)
T2 °F (°C)
102 to 105
32 to 37
(39 to 41)
(0 to 3)
106 to 106
32 to 36
(41 to 43)
(0 to 2)
– 25 –
FILE NO. SVM-13069
Indoor
Outdoor
fan mode
fan mode
High
High
High
High
Indoor
Outdoor
fan mode
fan mode
High
High
High
High
Compressor
revolution
(rps)
60
77
Compressor
revolution
(rps)
62
64