The P36D-10 is approved for a 40 ft. straight
vertical, with rigid pipe vent systems for Propane
and Natural Gas, as per the diagram 1.
The shaded area in the diagram 1 shows all
allowable combinations of straight vertical and
offset to vertical terminations with rigid pipe vent
systems for Propane and Natural Gas. Maximum
two 45
elbows allowed.
o
•
Vent must be supported at offsets
•
Firestops are required at each floor level
and whenever passing through a wall.
•
Maintain clearances to combustibles.
Diagram 1
®
Regency
P36D-10 Zero Clearance Direct Vent Gas Fireplace
installation
|
27
|