Electrical Service Guide; Placing Jumper Links - Miller Electric Dimension NT 450, NT 500 Owner's Manual

Arc welding power source
Table of Contents

Advertisement

4-12. Electrical Service Guide

Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.
50/60 Hertz Models
Input Voltage
Input Amperes At Rated Output
Max Recommended Standard Fuse Rating In Amperes
Min Input Conductor Size In AWG
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG
Reference: 2005 National Electrical Code (NEC)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 "Time-Delay" fuses are UL class "RK5" .
3 "Normal Operating" (general purpose − no intentional delay) fuses are UL class "K5" (up to and including 60 amp), and UL class "H" ( 65 amp and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

4-13. Placing Jumper Links

Tools Needed:
3/8 in
3/8 in
1
L1(U)
Connect
GND/PE
L2(V)
Conductor
L3(W)
First.
GND/PE
OM-2252 Page 20
1
2
Time-Delay
Normal Operating 3
4
4
Donot
overtighten
jumper linknuts.
3
Input
Contactor
2
230
380
400
57
34
33
70
40
40
90
50
50
6
8
8
145 (44)
256 (78)
284 (86)
8
10
10
230VOLTS
460VOLTS
440
460
575
30
29
23
35
35
25
45
40
35
10
10
10
226 (69)
243 (74)
380 (116)
10
10
10
!
Disconnect and lockout/tag-
out input
power
before
installing or moving jumper
links.
Check input voltage available at
site.
1
Jumper Link Label
Check label.
2
Jumper Links
Move jumper links to match input
voltage.
Close access door, or go on to
Section 4-14.
575VOLTS
S− 174973− B
Ref. 800 103-A

Hide quick links: