(2) Attach to the wall.
(a) Check the place for the hole using the included paper pattern for installation (3).
• Choose a place so that there is at least a 90 mm gap between the ceiling and the main unit.
(b) Temporarily attach the installation panel (1) at the temporary-securing position on the paper pattern
for installation (3) and use a level to make sure the drain hose is either level or tilted slightly downward.
(c) Secure the installation panel (1) to the wall using either screws or bolts.
• If using the attachment screws for the installation panel (2), attach using at least 4 screws on either
side (for a total of 9 screws) of the recommended installation cleat position on the included paper
pattern for installation (3).
• If using bolts, attach using a M8 - M10 bolt (for a total of 2 bolts) on either side.
• If dealing with concrete, use commercially available foundation bolts (M8 - M10).
(3) If using the left, bottom-left, right, or bottom-right positions for the piping, cut out the through-hole
for the piping in the front grill. (Refer to Fig. 4)
Right pipe
Bottom-right pipe
(4) Remove the front panel and the service lid. (Refer to Fig. 5)
< How to remove the front panel and service lid >
(1) Open the front panel to the point where it stops.
(2) Push the axes on either side of the front panel towards the center of the main unit and remove. (You can
also remove it by sliding the front panel either to the left or right and pulling it forward.)
(3) Remove the screw from the service lid and pull the handle forward.
English
Left pipe
Back-left pipe
Bottom-left pipe
Back-right pipe
Fig. 3
Axis
(2)
Axis
Front panel
(1)
Axis
(2)
Fig. 5
Front grill
Cut out along
the groove.
Cut away
Fig. 4
Service lid
(3)
Handle
Screw
6

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fayp71lv1Faq71buv1b

Table of Contents