The Heating Outlet Ntc Sensor Is Damaged - Worcester ZSBR 7-28 ICS1 Service Booklet

Table of Contents

Advertisement

E 2
flashing.

The heating outlet NTC sensor is damaged.

Check
B Activate menu option
1.
Show service parameters.
B Select .1 Flow temp.sensor.
Is a temperature between 0. and 5.
displayed?
2.
Heating outlet NTC sensor:
Temperature between 95. and 100. is
displayed.
3.
Check if the 20-pin connector lead
assembly is damaged.
4.
The PCB control board is damaged.
7 181 465 347 (01.07)
Action
yes:
The heating outlet NTC sensor is in short circuit:
B Power OFF the appliance.
B Replace CH flow NTC sensor; observe fitting
instructions for NTC sensor when doing so.
B Turn ON the appliance.
E2? ↓2.
↓ 2.
no:
yes:
The CH flow NTC sensor is interrupted:
B Power OFF the appliance.
B Replace CH flow NTC sensor; observe fitting
instructions for NTC sensor when doing so.
B Turn ON the appliance.
E2? ↓3.
↓3.
no:
B Power OFF the appliance.
B Change the 20-pin connector lead assembly.
B Turn ON the appliance.
E2? ↓4.
B Power OFF the appliance.
B Disconnect the boiler electrical connection.
B Change PCB control board.
B Reconnect the boiler electrical connection.
B Turn ON the appliance.
Rectifying faults
25