Technical Data - SMA Sunny Boy 1100 Installation Manual

Pv
Hide thumbs Also See for Sunny Boy 1100:
Table of Contents

Advertisement

SMA Solar Technology AG
11 Technical Data
PV generator connection data
Max. input voltage
Input voltage, MPP range
Max. input current
Max. input power
Recommended total generator power
Voltage ripple
Internal consumption during operation
a)
The maximum open circuit voltage, that can occur with - 10 °C cell temperature may not exceed the maximum
input voltage.
Grid connection data
Nominal output power
Peak output power
Nominal output current
Max. output current
Max. fuse protection
Harmonic distortion of output current
(at K
< 2 %, P
Ugrid
AC
Short-circuit tolerance
Nominal operating voltage
Voltage range
(extended operating range)
Nominal operating frequency
Frequency range
(extended operating range)
Power factor (at nominal output power)
Overvoltage category
Test voltage (DC)
Surge testing voltage
Internal consumption in night operation
Installation Guide
> 0.5 P
)
ACnom
SB 1100
U
DC max
U
PV
I
10 A
PV, max
P
1210 W
DC
1350 Wp
(for Central Europe)
U
< 10 % of the input voltage
PP
< 4 W (standby)
SB 1100
P
1000 W
AC, nom
P
1100 W
AC, max
I
4.4 A
AC, nom
I
5.6 A
AC, max
K
IAC
grid-side via current regulation
U
220 V / 230 V / 240 V
AC, nom
U
AC
f
AC, nom
f
50 Hz: 45.5 Hz ... 54.5 Hz
AC
60 Hz: 55.5 Hz ... 64.5 Hz
cos phi
(1 s routine testing / 5 s type testing)
4 kV (serial interface: 6 kV)

Technical Data

SB1700
a)
400 V
139 V ... 320 V
12.6 A
1850 W
2050 Wp
(for Central Europe)
< 5 W (standby)
SB 1700
1550 W
1700 W
6.7 A
8.6 A
16 A
< 3 %
180 V ... 260 V
50 Hz / 60 Hz
1
III
1.7 kV
0.1 W
SB11_17-IEN084820
39