USER GUIDE
SAFETY • INSTALLATION & INTEGRATION • OPERATING INSTRUCTIONS • MAINTENANCE • SERVICE
ID
Description
L Zone T
Left Zone thermistor
Short
circuit shorted.
R Zone T
Right Zone thermistor
Short
circuit shorted.
L Evap T
Left evaporator
Short
thermistor circuit short.
R Evap T
Right evaporator
Short
thermistor circuit short.
Amb
Ambient thermistor
Thrm
circuit shorted.
Short
L Temp
Left Zone temperature
Hi 6H+
+10°F (5°C) over set
point for over 6 hours.
R Temp
Right Zone
Hi 6H+
temperature +10°F
(5°C) over set point for
over 6 hours.
L Temp
Left Zone temperature
Hi 12H+
+10°F (5°C) over set
point for over 12 hours.
Solution
Check thermistor
connection to harness for
moisture or corrosion. Also
check connection where
thermistor harness
attaches to main board. If
connections are valid
replace the thermistor.
Check thermistor
connection to harness for
moisture or corrosion. Also
check connection where
thermistor harness
attaches to main board. If
connections are valid
replace the thermistor.
Check thermistor
connection to harness for
moisture or corrosion. Also
check connection where
thermistor harness
attaches to main board. If
connections are valid
replace the thermistor.
Check thermistor
connection to harness for
moisture or corrosion. Also
check connection where
thermistor harness
attaches to main board. If
connections are valid
replace the thermistor.
Check thermistor
connection to harness for
moisture or corrosion. Also
check connection where
thermistor harness
attaches to main board. If
connections are valid
replace the thermistor.
Is condenser coil clean? Is
condenser fan operating?
Check zone thermistor for
correct resistance. Verify
thermistor connections are
clean and intact. Check
zone valve operation.
Sealed system issue?
Is condenser coil clean? Is
condenser fan operating?
Check zone thermistor for
correct resistance. Verify
thermistor connections are
clean and intact. Check
zone valve operation.
Sealed system issue?
Is condenser coil clean? Is
condenser fan operating?
Check zone thermistor for
correct resistance. Verify
thermistor connections are
clean and intact. Check
zone valve operation.
Sealed system issue?
ID
Description
R Temp
Right Zone
Hi 12H+
temperature +10°F
(5°C) over set point for
over 12 hours.
L Temp
Left Zone temperature
Lo 6H+
-10°F (5°C) under set
point for over 6 hours.
R Temp
Right Zone
Lo 6H+
temperature -10°F
(5°C) under set point
for over 6 hours.
L Temp
Left Zone temperature
Lo 12H+
10°F (5°C) under set
point for over 12 hours.
R Temp
Right Zone
Lo 12H+
temperature +10°F
(5°C) under set point
for over 12 hours.
L Door
Left door switch open
Open 5M
for more then 5
minutes.
R Door
Right door switch open
Open 5M
for more then 5
minutes.
To access All Errors follow the steps below.
1. Press
to select "All Errors".
2. Press
.
3. Press
and
to scroll through available
information.
To clear the error log, press
and press
to confirm.
u-line.com
Solution
Is condenser coil clean? Is
condenser fan operating?
Check zone thermistor for
correct resistance. Verify
thermistor connections are
clean and intact. Check
zone valve operation.
Sealed system issue?
Verify thermistor
connections are clean and
dry. Verify thermistor
resistance. Verify correct
operation of zone valve.
Verify thermistor
connections are clean and
dry. Verify thermistor
resistance. Verify correct
operation of zone valve.
Verify thermistor
connections are clean and
dry. Verify thermistor
resistance. Verify correct
operation of zone valve.
Verify thermistor
connections are clean and
dry. Verify thermistor
resistance. Verify correct
operation of zone valve.
Check door switch magnet
reed switch alignment
when door is in closed
position. Check reed switch
connection at the harness
and the main board.
Check door switch magnet
reed switch alignment
when door is in closed
position. Check reed switch
connection at the harness
and the main board.
to select "Clear Errors"