Fault messages on the display
Fault code
System character-
on the dis-
istics
play
F4
Burner in a fault
state
F8
Burner in a fault
state
F9
Burner in a fault
state
FA
Burner in a fault
state
FC
Burner blocked
Fd
Burner blocked
(cont.)
Cause
Measures
No flame signal is
Check the ionisation
present
electrode and leads,
measure the ionisation
current, check the gas
pressure, check the gas
train, ignition, ignition
module and condensate
drain.
Press "Reset" (see
page 36).
The fuel valve
Check the gas train.
closes too late
Check both control
paths.
Press "Reset" (see
page 36).
Fan speed too
Check the fan, check
low during the
the fan cables and sup-
burner start
ply; check the fan con-
trol.
Press "Reset" (see
page 36).
Fan not at stand-
Check the fan, fan con-
still
necting cables and fan
control.
Press "Reset" (see
page 36).
Control unit or
Replace boiler coding
boiler coding card
card or control unit
faulty
Burner control
Check ignition electro-
unit fault
des and connecting
cables. Check whether a
strong interference
(EMC) field exists near
the equipment.
Press "Reset" (see
page 36).
Replace control unit if
the fault persists.
Troubleshooting
35