Troubleshooting
Fault messages on the display
Fault code
System character-
on the dis-
istics
play
5A
Burner blocked
A9
Regulated operation
without Open Therm
device
b0
Burner blocked
b8
Burner blocked
E5
Burner blocked
E6
Burner blocked
F0
Burner blocked.
F1
Burner in a fault
state
F2
Burner in a fault
state
F3
Burner in a fault
state
34
(cont.)
Cause
Measures
Flow sensor lead
Check connections and
broken
lead; replace sensor if
required.
Communication
Check connections and
fault Open Therm
lead; replace Open
device
Therm device if re-
quired.
Flue gas tem-
Check the sensor (see
perature sensor
page 43).
shorted out
Flue gas tem-
Check the sensor (see
perature sensor
page 43).
lead broken
Internal fault
Check the ionisation
electrode and cables.
Press "Reset" (see
page 36).
Water pressure
Top up with water.
too low
Internal fault
Replace the control unit.
Max. flue gas
Check the flue gas sys-
temperature ex-
tem.
ceeded
Press "Reset" (see
page 36).
The temperature
Check the heating sys-
limiter has re-
tem fill level. Check the
sponded
circulation pump. Vent
the system. Check the
temperature limiter and
connecting cables.
Press "Reset" (see
page 36).
Flame signal is al-
Check the ionisation
ready present at
electrode and connect-
burner start
ing cable.
Press "Reset" (see
page 36).